3. SIGNALS AND WIRING

(b) Torque limit value selection

Choose the torque limit made valid by the internal torque limit value 1 (parameter No. 28) using the
external torque limit selection (TL) or the torque limit made valid by the analog torque limit (TLA)
as indicated below:

Torque Limit Value Made Valid

(Note) TL

If TLA > Parameter No. 28

If TLA < Parameter No. 28

0

Internal torque limit value 1

(parameter No. 28)

1

Internal torque limit value 1

(parameter No. 28)

Analog torque limit (TLA)

Note. 0 : TLA-SG off (open)

1 : TLA-SG on (short)

(c) Limiting torque (TLC)

TLC-SG are connected when the torque generated by the servo motor reaches the torque set to
internal torque limit value 1 or analog torque limit.

(3) In-position (INP)

PF-SG are connected when the number of droop pulses in the deviation counter falls within the preset
in-position range (parameter No. 5). INP-SG may remain connected when low-speed operation is
performed with a large value set as the in-position range.

Servo-on (SON)

Alarm

Droop pulses

In position (INP)

ON

OFF

Yes

No

In-position range

ON

OFF

(4) Ready (RD)

Servo-on (SON)

Alarm

Ready (RD)

ON

OFF

Yes

No

80ms or less

10ms or less

10ms or less

ON

OFF