Fireplace framing specifications, Figure 9 figure 8 – Miele MNTSVBE User Manual

Page 6

Advertising
background image

6

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

Figure 6

Figure 7

10 ft.

Minimum

12 ft.

Minimum

60 degrees

max.

Slip the first 6 inch (152 mm) section of B-
Vent over the fireplace flue outlet and secure
with four sheetmetal screws (# 8 or larger),
and install the remainder of the B-Vent to the
outside. Minimum overall height of the vent
system and appliance must be 10' (2.54 m)
vertical - no offset

(see Figure 6 ); or 12' (3.7

m) when an offset up to 60 degrees from the
vertical is used - this offset may start at the
fireplace flue collar

(see Figure 7 ). The

maximum overall height of the vent system
and appliance should not exceed 40 feet
.

Install the B-vent system in accordance with
the vent manufacturer's instructions.

CAUTION: THIS APPLIANCE CANNOT BE
VENTED HORIZONTALLY.

Note: Refer to the vent manufacturers in-
stallation instructions for variations of vent-
ing techniques. If common venting of sev-
eral units is contemplated, it should be dis-
cussed with an architect and the local Build-
ing Department.

Do not place insulation materials within 1 in.
of the gas vent system.

FIREPLACE FRAMING SPECIFICATIONS

Figure 9

Figure 8

Gas Line

Center of gas line

is 3 in. (76 mm)

up from floor.

*41

¹⁄₂

(1054)

41

¹⁄₂

(1054)

*This dimension can be reduced to 41 inches (1041 mm). This results in 0 in. (0 mm)
clearance between framing and unit framing spacers. (The 41

¹⁄₂ in. dimension permits

easier fireplace installation, if unit is installed after framing is erected.)

22

³⁄₄**

(578)

EBVST
(See-Through)

inches (millimeters)

6

¹⁄₄

(159)

Minimum Framing
Stud size is 2 x 4

**Based on 5/8” drywall. Use 23” for 1/2” drywall.

*41

¹⁄₂

(1054)

40

¹⁄₈

(1019)

EBVPF
(Peninsula)

inches (millimeters)

Gas Line

Center of gas line

is 3 in. (76 mm)

up from floor.

6

¹⁄₄

(159)

Minimum Framing
Stud size is 2 x 4

*This dimension can be reduced to 41 inches (1041 mm). This results in 0 in. (0 mm)
clearance between framing and unit framing spacers. (The 41

¹⁄₂ in. dimension permits

easier fireplace installation, if unit is installed after framing is erected.)

22

³⁄₄**

(578)

**Based on 5/8” drywall. Use 23” for 1/2” drywall.