Heater and fan control and external LEDs connector (CN2)
Status for PV-5127 can be shown on external LEDs. These must be connected to CN2 by a 10

position ribbon cable with a mating connector. Furthermore, the +5V Standby and logical outputs

for the external heating element and the external fan are placed in this connector. The layout of this

connector is shown in the schematic to the left of the connector. The function of the individual

LEDs is shown in the table:

LED name

Pin no Function

GND

1

System GND.

Mode_Green_LED

2

See note.

Heat_On

3

Logical output for external heat element, 3.3V when active.

Mode_Red_LED

4

See note.

Battery_LED

5

See section

Battery monitor and charger

.

Mains_OK_LED

6

On when mains supply OK.

Hot_LED

7

See section

UPS control.

Fan_On

8

Logical output for external fan, 3.3V when active.

Cold_LED

9

See section

UPS control.

+5V_STB

10

+5V standby, is active when the main DC/DC converter is on.

Note: Mode_Green_LED and Mode_Red_LED are intended for use with a two-color red+green

LED. When both Mode LEDs are on, you get yellow. The possible colors are:

Mode LED color

Function

Green

On, both +5V and +12V are on

Yellow

Standby, only +5V Standby is on

Off

Off, main DC/DC converter is off

The LEDs should be connected like this:

RS232 connector (CN3)
This connector is documented in the UPS Control section.