Johnson Controls CP8C/CPLC*MP User Manual

Page 9

Advertising
background image

368262-UIM-B-1008

Johnson Controls Unitary Products

9

SECTION III: FILTERS

FILTER INSTALLATION

All applications require the use of a field installed filter. All filters and
mounting provision must be field supplied.

Filters must be installed external to the furnace cabinet. DO NOT
attempt to install filters inside the furnace.

NOTES:

1. Air velocity through throwaway type filters may not exceed 300 feet per

minute (91.4 m/min). All velocities over this require the use of high velocity
filters.

2. Do not exceed 1800 CFM using a single side return and a 16x25 filter. For

CFM greater than 1800, you may use two side returns or one side and the
bottom or one side return with a transition to allow use of a 20x25 filter.

SIDE RETURN

Locate the “L” shaped corner locators. These indicate the size of the cut-
out to be made in the furnace side panel. Refer to Figure 15.

Install the side filter rack following the instructions provided with that
accessory. If a filter(s) is provided at another location in the return air
system, the ductwork may be directly attached to the furnace side
panel.

FIGURE 14: Dimensions

LEFT SIDE

RIGHT SIDE

.5”

.5”

RETURN END

B

24.25”

29.5”

(For Cladded door add appoximately an additional .75”)

28.5”

Electrical
Entry

Gas Pipe
Entry

Thermostat
Wiring

FRONT

14”

1”

1.5”

23”

SUPPLY END

C

24.38”

20”

.5”

B

Gas Pipe
Entry

Thermostat
Wiring

33”

A

.5”

Electrical
Entry

Vent Connection
Outlet

Vent
Connection
Outlet

4” Diameter

Outlet

Vent Connection

Table 3: Cabinet and Duct Dimensions

BTUH (kW)

Input

Nominal

CFM (m

3

/min)

Cabinet

Size

Cabinet Dimensions (Inches)

Approximate

Operating Weights

A

A (cm)

B

B (cm)

C

C (cm)

Lbs

60 (17.6)

1200 (34.0)

A

14 1/2

36.8

13 1/2

34.3

10.3

26.2

94

80 (23.4)

1200 (34.0)

B

17 1/2

44.4

16 1/2

41.9

11.8

29.9

103

80 (23.4)

1600 (45.3)

C

21

53.3

20

50.8

13.6

34.5

114

100 (29.3)

1600 (45.3)

C

21

53.3

20

50.8

13.6

34.5

118

100 (29.3)

2000 (56.6)

C

21

53.3

20

50.8

13.6

34.5

122

120 (35.1)

2000 (56.6)

C

21

53.3

20

50.8

15.8

40.1

129

Table 4: Recommended Filter Sizes (High Velocity 600 FPM)

CFM

(m³/min)

Cabinet

Size

Side

(in)

Bottom

(in)

1200 (34.0)

A

16 x 25

14 x 25

1200 (34.0)

B

16 x 25

16 x 25

1600 (45.3)

C

16 x 25

20 x 25

2000 (56.6)

C

(2) 16 x 25

20 x 25

FIGURE 15: Side Return Cutout Markings

Some accessories such as electronic air cleaners and pleated
media may require a larger side opening. Follow the instructions
supplied with that accessory for side opening requirements. Do not
cut the opening larger than the dimensions shown in Figure 14.

Front of
Furnace

Corner
Markings

Side of
Furnace

Advertising
This manual is related to the following products: