ECONOMIZER MODULE

62-0331—11

2

INSTALLATION AND SETUP

The Economizer module may be mounted in any orientation.

However, mounting in the orientation shown above permits

proper viewing of the LCD display and use of the keypad.

NOTE: Jade will be in the “set up” mode for the first 60

minutes after powered. If a sensor for OA air or

Sylkbus device (sensor, actuator) is discon-

nected during the set up mode, the Jade will not

alarm that failure. The MA sensor is a system

“critical” sensor; if the MA sensor is removed

during the set up mode, the Jade will alarm. After

60 minutes the Jade controller will change to

operation mode and all components removed or

failed will alarm in the operation mode.

WIRING

All wiring must comply with applicable electrical codes and

ordinances, or as specified on installation wiring diagrams.

Module wiring in the field is terminated to the four screw

terminal blocks located on the left and right sides.

Module wiring at the OEM factory is terminated via the header

pin terminals located on the left and right sides. The header

terminal pins and the terminal blocks have common

terminations for the appropriate input or output. The part

number for the OEM female mating connector is 0039973997.

WARNING

Electrical Shock Hazard.

Can cause severe injury, death or property

damage.

Disconnect power supply before beginning wiring, or

making wiring connections, to prevent electrical shock

or equipment damage.

CAUTION

Equipment Damage Hazard.

Electrostatic discharge can short equipment

circuitry.

Ensure that you are properly grounded before

handling the unit.

Each terminal can accommodate the following gauges of wire:

• Single wire – from 18 AWG to 22 AWG solid or stranded

• Multiple wires – up to two 22 AWG stranded

• For the 24 Vac connections: single wire – from 14 to 18

AWG solid or stranded

For S-BUS wiring, the sensors may be mounted up to 200 ft.

(61 m) from the JADE controller. When the length of wire is

over 100 feet use twisted pair shielded wire.

NOTE: All wiring is polarity insensitive.

Refer to Fig. 1 through Fig. 6 for common wiring

configurations.

Actuator Wiring Options:

1. The JADE economizer controller can only have one (1)

communicating actuator connected to it.

2. Up to four (4) non-communicating and (2) 2-position

actuators (1 each on EXH1 and AUX1 O)

3. One (1) communicating and up to four (4) non-commu-

nicating and (2) 2-position actuators (1 each on EXH1

and AUX1 O)

When using a 2-position actuator on the AUX1 O the AUX1 O

must be programmed for Exh2 and the % open is the % open

of the outdoor damper when the 2-pos actuator opens.

Connect 24 V to Exh1 and/or AUX1 O and ground to the Jade

“C” terminal.

Note the W7220 economizer will not work with an old “black

motor” M7415; replace the M7415 with a M7215 or MS3103

DCA.

Table 1. Economizer Module - Left hand terminal blocks.

Label

Type

Description

Top Left Terminal Block

MAT

MAT

20k NTC

and COM

Mixed Air Temperature Sensor

(polarity insensitive connection)

OAT

OAT

20k NTC

and COM

Outdoor Air Temperature Sensor

(polarity insensitive connection)

S-BUS

S-BUS

SYLK Bus Sylk Bus sensor

(polarity insensitive connection)

Bottom Left Terminal Block

IAQ 2-10

2-10 Vdc

Air Quality Sensor Input

(e.g. CO

2

sensor)

IAQ COM COM

Air Quality Sensor Common

IAQ 24V

24 Vac

Air Quality Sensor 24 Vac Source

ACT 2-10

2-10 Vdc

Damper Actuator Output (2-10 Vdc)

ACT COM COM

Damper Actuator Output Common

ACT 24V

24 Vac

Damper Actuator 24 Vac Source

Table 2. Economizer Module - Right hand terminal blocks.

Label

Type

Description

Top Right Terminal Block

n/a

The first terminal is not used

AUX2 I

24 Vac IN

Shut Down (SD) or Heat (W)

Conventional only or

Heat Pump Changeover (O/B) in

Heat Pump mode.

OCC

24 Vac IN

Occupied / Unoccupied Input

E-GND

EGND

Earth Ground - System Required

EXH1

24 Vac OUT Exhaust Fan 1 Output

AUX1 O

24 Vac OUT Programmable:

Exhaust fan 2 output or

ERV or System Alarm output.

Bottom Right Terminal Block

Y2-I

24 Vac IN

Y2 in - Cooling Stage 2 Input from

space thermostat

Y2-O

24 Vac OUT Y2 out - Cooling Stage 2 Output to

stage 2 mechanical cooling

Y1-I

24 Vac IN

Y1 in - Cooling Stage 1 Input from

space thermostat

Y1-O

24 Vac OUT Y1 out - Cooling Stage 1 Output to

stage 1 mechanical cooling

C

COM

24 Vac Common

R

24 Vac

24 Vac Power (Hot)