Jade, Economizer module – Jade Range W7220 User Manual

Page 4

Advertising
background image

JADE

ECONOMIZER MODULE

62-0331—11

4

Fig. 2. Stand-alone dry-bulb Economizer configuration with Honeywell MS7403 Direct Coupled Actuator.

ROOF TOP UNIT

Y1O

Y2O
Y1I

Y2I

OCC

24 VAC

E-GND

Y1

G

W2

W1

Y2

O/B

OCC

W7220 ECONOMIZER CONTROLLER MODULE

THERMOSTAT

CO2

SENSOR

2-10 VDC

(OPTIONAL)

MAT

MAT

OAT

OAT

C R

M32564D

IAQ (2-10V)

IAQ COM

IAQ 24V

ACT (2-10V)

ACT COM

ACT 24V

3

OAT TEMP

SENSOR

20K NTC

MS7503 OR MS7505

NOTE THAT THE 20K NTC SENSOR CAN BE MOUNTED IN THE OAT TERMINALS ONLY IN THIS CONFIGURATION

.

WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O

OR B AND W2 MAY BE LABELED W.

WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.

1

1

MA TEMP

SENSOR

20K NTC

R(+)

C(-)

AUX1-0

AUX2-I

2

3

2

3

1K1

1K1

Advertising