Compatibility
Table 4 lists compatible tools, Operating Systems, and
controllers used over the Zone Bus and N2 Bus with
the CVTPRO converter.

Compatible controllers include the Air Handling Unit
(AHU), Unitary Controller (UNT), Variable Air Volume
Controller (VAV), Network Dialer Module (NDM),
and VMA.

Table 4: Compatibility Chart

Tool

Bus

Operating System

Compatible Controller

N2 Bus

Windows 98 SE/Windows NT

1

/

Windows 2000PE

2

OS

Zone Bus

Windows 98 SE/Windows 2000PE

2, 3

OS

AHU1xx
UNT1xx
UNT11xx
VAV1xx
VMA14x0

HVAC PRO Software (part of
M-Tool Release 5.0 or later)

Zone Bus

Windows NT

1

VMA14x0*

VBT1400

Zone Bus

Palm Personal Digital Assistant (PDA)
with OS Version 3.5 or later

VMA14x0

VBT1200

Zone Bus

Palm PDA with OS Version 2.x or later

VMA12x0

GX-9100 Software
Configuration Tool (part of
M-Tool Release 5.0 or later)

N2 Bus

Windows 98 SE/Windows NT

1

/

Windows 2000PE

2

OS

DT-9100
DX-9100
XT9100 (XP91xx)
XTM-905 (XPx-xxx)

XTM Configuration Tool

N2 Bus

Windows 98 SE/

1

Windows NT

1

/

Windows 2000PE

2

OS

XTM-105 (XPx-xxx)

NDM Configuration Tool

N2 Bus

Windows 98 SE/

Windows NT

1

/

Windows 2000PE

2

OS

NDM

Note:

The CVTPRO converter is not compatible with Zone Terminal Units (ZTUs). For ZTUs, use the CBLPRO-2
converter. See the Auxiliary Gear Technical Bulletin (LIT-6363080) for details on Johnson Controls® converters.

1

For proper CVTPRO converter operation when running on Windows NT OSs, Service Pack 6 must be installed.

2

For proper CVTPRO converter operation when running on Windows 2000 OSs, use the Professional Edition only, and
Service Pack 2 must be installed.

3

On Zone Bus applications running on Windows 2000 OSs, HVAC PRO Version 8.04B or later must also be installed.

*

When using the VMA14x0 with HVAC PRO software (versions prior to Version 8.04B only) over the Zone Bus with
Windows NT OSs, a Device Conflict box appears whenever the user attempts an operation (for example, upload or
download). To bypass the box, select Yes or No and the box disappears. The selected operation continues as
expected.

Battery Power Recommendations
The CVTPRO converter requires two (user-supplied)
AAA alkaline type batteries on N2 Bus applications
(when the External Power Adapter is not used).
Battery life varies depending on the N2 Bus load,
ambient temperature and type of batteries. See
Table 5 and observe the following guidelines.

Always have a spare set of new batteries on hand.

When performing long downloads with the

CVTPRO converter, use the External Power
Adapter instead of batteries.

Table 5: *Typical Battery Life in CVTPRO Converter

AAA Battery:
Manufacturer
and Model/Type

Battery Life

Ray-O-Vac® Industrial Plus

4-1/2 hours

Duracell® CopperTop

5-1/2 hours

Eveready® Energizer Max®

6-1/2 hours

*

using a CVTPRO converter in continuous operation
on a fully loaded N2 Bus at room temperature (70

°

F

[21

°

C])