Johnson Controls ACPU024 THRU 060 User Manual

Page 21

Advertising
background image

279815-PTG-D-0408

Johnson Controls Unitary Products

21

060

(5.0)

208/230-1-60

25.0

150

39

2.3

7.6

None

-

-

-

41.2

50

2NH04501006

7.5 / 10

2

36.1 / 41.7

54.6 / 61.6

60 / 70

2NH04501506

11.3 / 15

2

54.2 / 62.5

77.2 / 87.6

80 / 90

2NH04502006

15 / 20

2

72.2 / 83.3

99.8 / 113.7

100 / 125

2NH04502506

18.8 / 25

2

90.3 / 104.2 122.3 / 139.7

125 / 150

208/230-3-60

17.3

123

27

2.3

7.6

None

-

-

-

31.5

40

2NH04501025

7.5 / 10

1

20.8 / 24.1

35.6 / 39.6

45 / 45

2NH04501525

11.3 / 15

1

31.3 / 36.1

48.6 / 54.6

50 / 60

2NH04502025

15 / 20

2

41.7 / 48.1

61.6 / 69.6

70 / 70

2NH04502525

18.8 / 25

2

52.1 / 60.1

74.7 / 84.7

80 / 90

460-3-60

8.4

70

13

1.3

3.8

None

-

-

-

15.6

20

2NH04501046

10

1

12

19.8

20

2NH04501546

15

1

18

27.3

30

2NH04502046

20

2

24.1

34.8

35

2NH04502546

25

2

30.1

42.3

45

1. Minimum Circuit Ampacity.
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker size installed at factory or field installed.

TABLE 11: ACP024-060 ELECTRICAL DATA / ELECTRIC HEAT (CONTINUED)

Size

(Tons)

Volt

Compressors

(each)

OD

Fan

Motors

(each)

Supply
Blower

Motor

Electric Heat Option

MCA

1

(Amps)

Max Fuse

2

/

Breaker

3

Size

(Amps)

RLA LRA MCC

FLA

FLA

Model

kW

Stages

Amps

Advertising