4 center of gravity, 12 unit weights, Clearances – Johnson Controls ACPU024 THRU 060 User Manual

Page 23

Advertising
background image

279815-PTG-D-0408

Johnson Controls Unitary Products

23

FIGURE 4 - CENTER OF GRAVITY

NOTE: For units applied with a roof curb, the minimum

clearance may be reduced from 1 inch to 1/2 inch

between combustible roof curb material and the supply
duct.

TABLE 12: UNIT WEIGHTS

Unit Size

Shipping

Weight

Operating

Weight

Corner Weights

Economizer

(lbs.)

Roof Curb

(lbs.)

A

B

C

D

024

338

333

91

80

78

88

40

8" - 70

14" - 75

030

340

335

86

83

83

87

036

360

360

96

84

81

93

042

348

343

94

83

80

91

048

384

379

103

90

87

99

060

500

495

135

117

113

130

26

FRONT

OF

UNIT

A

B

C

D

CENTER OF GRAVITY

TABLE 13: CLEARANCES

Unit Clearances

(Minimum)

Front

12"

Back

0"

Left Side (Filter Access)

24"

Right Side

24"

Below Unit

1

1. Units may be installed on combustible floors made from wood

or class A, B or C roof covering material.

0"

Above Unit

2

2. Units must be installed outdoors. Overhanging structures or

shrubs should not obstruct outdoor air discharge outlet.

36" (For Condenser Air

Discharge)

3'

FLEXIBLE DUCT

COLLAR

Minimum clearance of 1" all sides
for the first 3' of duct for 20 & 25
kW. Zero inches thereafter, for all
other heaters, zero inch clearance
all sides for entire length of duct.