Johnson Controls XP-910x User Manual

Page 35

Advertising
background image

Configuration Guides—XT-9100 Configuration Guide 35

RI.

HI.

Type

R/W

Tag

Description

88

58

2 Bytes

CNF

AIT1

Input Type of Analog Input 1

0 0 0 0 0 X11 X10 X9

X8 X7 X6 X5 X4 X3 X2 X1

X4 X3 X2 X1

Unit of Measure

= 0000

No Units

= 0001

Degrees Celsius or Kelvin

= 0010

Degrees Fahrenheit

= 0011

Percent

X5 = 1

Enable Square Root of Input

X6 = 1

Alarm on Unfiltered Value

X7 = 0

0-10 Volts

X7 = 1

0-2 Volts, 0-20 mA or RTD

X8 = 1

20 % Suppression

X11 X10 X9

Linearization and Sensor Type

= 000

Linear (active sensor)

= 001

Nickel 1000 (JCI)

= 010

Nickel 1000 Ext. Rng

= 011

A99 Sensor

= 100

PT1000 Sensor

89

59

Number

CNF

HR1

High Range Analog Input 1

90

5A

Number

CNF

LR1

Low Range Analog Input 1

91

5B

Number

R/W (E)

HIA1

High Alarm Limit Analog Input 1

92

5C

Number

R/W (E)

LOA1

Low Alarm Limit Analog Input

93

5D

Number

R/W (E)

ADF1

Differential on Alarm Limit [units]

94

5E

Number

CNF

FTC1

Filter Constant Analog Input 1

95

5F

2 Bytes

Spare

96

60

2 Bytes

CNF

AIT2

Input Type of Analog Input 2 (bits
as AIT1)

97

61

Number

CNF

HR2

High Range Analog Input 2

98

62

Number

CNF

LR2

Low Range Analog Input 2

99

63

Number

R/W (E)

HIA2

High Alarm Limit Analog Input 2

100

64

Number

R/W (E)

LOA2

Low Alarm Limit Analog Input 2

101

65

Number

R/W (E)

ADF2

Differential on Alarm Limit [units]

102

66

Number

CNF

FTC2

Filter Constant Analog Input 2

103

67

2 Bytes

Spare