Johnson Controls XP-910x User Manual

Page 5

Advertising
background image

Configuration Guides—XT-9100 Configuration Guide 5

XP9103

DO 1
DO 2
DO 3
DO 4
DO 5
DO 6
DO 7
DO 8

XP9102

ADDRESS

A B C

A B C

RD
TD

Power

RS485

FU S E

HOT GND NEUT

E X P

E X P

F U S E

min

max

XT9100

TR9100

E X P

E X P

max
AO7

AO8

min

E X P

Bus Connector (provided)

emtxt-4

D O 5 D O 6 D O 7 D O 8

A I5 A I6 V

AO 7

A O 8

2 4 V

C

2 4 V

C O M

2 4 V

C O M

DO1

DO2

DO3

DO4

+ 1 5 V

A I 1 A I 2 A I 3 A I 4

XT

XP1

XP2

TR

Figure 2: Typical XT-9100 Configuration

Table 2: XT Configurations

TR

Transformer

TR-9100

(optional)

XT

Processor

XT-9100

XP1

Analog

or

Digital

XP-9102

XP-9103

XP-9104

XP-9105

1 or 2 x XP-9106

(See Note 1.)

(See Notes 2 and 4.)

XP2

Digital

XP-9103

XP-9104

XP-9105

1 or 2 x XP-9106

(optional)

(optional)

(optional)

(optional) (See Notes 2, 3, and 4.)

Notes:

1.

The analog XP-9102 must be placed in position XP1.

2.

Two XP-9106 modules are considered as one XP module when installed next to each
other in Position XP1 or XP2. When a single XP-9106 is installed in Position XP1 and
another type of XP module is installed in Position XP2, the total number of I/Os is
restricted to 12.

3.

The XP-9106 can only be placed in Position XP2 when Position XP1 is filled by an
analog XP or two XP-9106 modules.

4.

The first XP-9106 in position XP1 or XP2 controls points DO1-DO4 and the second
XP-9106 in either position controls points DO5-DO8.

5.

Digital modules with counters must be in position XP1.

Advertising