Quickspecs – Server Technology QUICKSPECS BL20P User Manual

Page 33

Advertising
background image

Max total power
supported

3000 W

9000 W

15,000 W

Total max input current
at minimum voltage

69.44 A at -43.2VDC

208.32 A at -43.2 VDC 347.2 A at -43.2 VDC

(equivalent of 175A
per feed)

Total max input current
at nominal voltage

62.5 A at -48VDC

187.5 A at -48 VDC

312.5 A at -48 VDC
(equivalent of 175A
per feed)

Max current per power
feed

70A

210A

210A

Max local ambient
temperature

149° F (65° C)

149° F (65° C)

NOTE: All systems support redundant A & B feeds. Scalable bus bar supports dual A and dual B
feeds.

Operating and
Performance
Specifications for
Facility DC

Voltage

Nominalinput voltage

-48 VDC

Operating voltage range

-48VDC ± 10% or -43.2 VDC to -52.8 VDC

Max input voltage slew
rate

0.5V/uS

Redundant feed voltages* *A and B feeds must differ by no more than

5VDC during steady state operation

Ripple/Noise

480 mV PARD**

Overshoot

Must remain within regulation limits on all
feeds during startup or shutdown

Voltage Transients

Must not exceed -60 VDC

Current

Max steady state input
current

62.5A per server blade enclosure installed at
-48VDC

Max steady state current
per feed/total

Power bus boxes

70 A/70A

Mini bus bars

210 A/210A

Scalable bus bars

210 A/350A or equivalent of 175A per feed*

In-rush current

Must support up to 2X the maximum operating current per server blade
enclosure (125 A) for up to 1.0 mS

Input over-current

Customer provided fusing for facility DC feeds that protects the system
from catastrophic over-current within 20 uS. Fuse should sustain all in-
rush and operating currents.

Max Input Current
Slew Rate

1A/uS

Max Input Curent Slew
Rate

3000W per server blade enclosure

Connection and
Cables

HP provided facility DC cable connection kit:

The facility DC connection kit supports the connection of up to four
-48VDC, RETURN pairs and ground.

The power cable assemblies consist of 1/0AWG, color-coded, flexible
cable rated at 105° C, terminated with bus mating connectors at one end
and unterminated at the other end. The cable length provided enables
the customer to route to a fuse panel within or adjacent to the rack.

NOTE: *All systems support redundant A and B feeds. Scalable bus bars support dual A and dual
B feeds.
** Periodic and random noise (PARD). Maximum allowable peak-to-peak ripple and noise (as

QuickSpecs

HP ProLiant BL20p p-Class Server Blade

Technical Specifications

DA - 11411 Worldwide QuickSpecs — Version 24 — 9.24.2004