System Sensor DH100ACDCLP User Manual

Page 8

Advertising
background image

D200-14-00 8 I56-0084-06R

©

2003 System Sensor

Three-Year Limited Warranty

System Sensor warrants its enclosed air duct smoke detector to be free from

defects in materials and workmanship under normal use and service for a period

of three years from date of manufacture. System Sensor makes no other express

warranty for this air duct smoke detector. No agent, representative, dealer, or

employee of the Company has the authority to increase or alter the obligations

or limitations of this Warranty. The Company’s obligation of this Warranty shall

be limited to the repair or replacement of any part of the air duct smoke detector

which is found to be defective in materials or workmanship under normal use and

service during the three year period commencing with the date of manufacture.

After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a

Returns Authorization number, send defective units postage prepaid to: System

Sensor, Returns Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL

60174. Please include a note describing the malfunction and suspected cause of

failure. The Company shall not be obligated to repair or replace units which are

found to be defective because of damage, unreasonable use, modifications, or

alterations occurring after the date of manufacture. In no case shall the Company

be liable for any consequential or incidental damages for breach of this or any

other Warranty, expressed or implied whatsoever, even if the loss or damage is

caused by the Company’s negligence or fault. Some states do not allow the exclu-

sion or limitation of incidental or consequential damages, so the above limitation

or exclusion may not apply to you. This Warranty gives you specific legal rights,

and you may also have other rights which vary from state to state.

[9] Model DH100ACDCLP Air Duct Smoke Detector Specifications
Operating Temperature: +32° to +131° F 0° to +55° C
Storage Temperature: –22° to +158° F –30° to +70° C
Humidity: 10% to 93% R.H. noncondensing
Air Velocity: 100 to 4000 ft./min. 0.5 to 20.3 m/sec.
Dimensions: 14.38” L x 5.5” W x 2.75” D 37cm L x 14cm W x 7cm D

Weight: 3.75 pounds 1.7 kg
Electrical Specifications
Power supply voltage: 20-29 VDC 24 VAC 50-60-Hz 120 VAC 50-60 Hz 220/240 VAC 50-60 Hz
Input capacitance: 270 µF max. 270 µF max. N/A N/A
Reset voltage: 3.0 VDC min. 2.0 VAC min. 10 VAC min. 20 VAC min.
Reset time (with RTS451): .03 to 0.3 sec. .03 to 0.3 sec. .03 to 0.3 sec. .03 to 0.3 sec.
Reset time (by power down): 0.6 sec. max. 0.6 sec. max. 0.6 sec. max. 0.6 sec. max.
Power up time: 34 sec. max. 34 sec. max. 34 sec. max. 34 sec. max.
Alarm response time: 2 to 17 sec. 2 to 17 sec. 2 to 17 sec. 2 to 17 sec.
Sensitivity Test: See detector label See detector label See detector label See detector label

loosen and blow out any remaining debris. Replacement
screens (S08-39-01) are available.

3. Vacuum photo chamber, then use clean compressed air

to blow area clean.

4. Replace the chamber by pressing it onto the base.

Press the screen into place. It should fit tightly on the
chamber.

[8.0] Board Replacement
[8.1] Detector Board Replacement (part no. A5069)
1. Remove the two detector board mounting screws.
2. Pull gently on the board to remove it.

3. To replace the board, align the board mounting fea-

tures, holes, and the interconnect terminals. Push the
board into place.

4. Secure board with the two mounting screws.

[8.2] Power Board replacement (part no. A5064)
1. Disconnect wiring from the terminal block.
2. Remove the two power board mounting screws.
3. Pull gently on the board to remove it.
4. To replace the board, align the board mounting fea-

tures, holes, and the interconnect terminals. Push the
board into place.

5. Secure board with the two mounting screws.
6. Re-connect wiring to terminal block.

Power Supply Voltage

20 - 29 VDC

24 VAC 50 - 60 Hz

120 VAC 50 - 60 Hz

220/240 VAC 50 - 60 Hz

CURRENT REQUIREMENTS (USING NO ACCESSORIES)

Max. standby current

15 mA

35 mA RMS

25 mA RMS*

15 mA RMS*

Max. alarm current

70 mA

125 mA RMS

35 mA RMS*

25 mA RMS*

CONTACT RATINGS

Alarm initiation contacts (SPST)

2.0A @ 30 VDC (resistive)

Alarm auxiliary contacts (DPDT)

10A @ 30 VDC
10A @ 250 VAC
1/4 HP @ 240 VAC
1/8 HP @ 120 VAC

Trouble contacts (SPDT)

2.0A @ 30 VDC (resistive)
2.0A @ 125 VAC (resistive)

Note:

Alarm auxiliary contacts must switch 100 mA minimum at 5VDC. Alarm auxiliary contacts shall not be
connected to inititaing circuits of control panels. Use the alarm initiation contact for this purpose.

* NOTE: When a unit is powered at the 120VAC or 220/240VAC input, any

combination of accessories may be used such that the given accessory loads are:

60 mA or less in the standby state,

110 mA or less in the alarm state.

ACCESSORY CURRENT LOADS AT 24 VDC
DEVICE
APA451
PA400
RA400Z
RTS451
RTS451KEY
SSK451

STANDBY
12.5mA Max.
0mA
0mA
0mA
12mA*
5mA Max.

ALARM
30mA Max.
15mA Max.
10mA Max.
7.5mA Max.
7.5mA Max.
30mA Max.

TROUBLE
n/a
n/a
n/a
n/a
n/a
9mA Max.

Please refer to insert for the Limitations of Fire Alarm Systems

H0164-00