Auto address setting, Test run – Sanyo CHX06052 User Manual

Page 11

Advertising
background image

1-7

Test Run

1

3. Auto Address Setting

1-1

1-2

2-1

2-2

2-7

1-3

1-6

2

7

7

ON

1

2

ON

OFF

Automatic address setting in Heating mode

Automatic address setting in Cooling mode

*

When multiple outdoor units exist, remove the socket that
is used to short-circuit the terminal plug (CN33) from all
outdoor unit PCBs except for 1.

Alternatively, move the sockets to the “OPEN” side.

Leave the socket
that is used to
short-circuit the
terminal plug.
(CN33)

To other system
link wiring

Case 2

Case 1

Case 3

Make settings as appropriate for the cases listed below.

(Refer to the instructions on the following pages.)

Leave the socket
that is used to open
circuit the terminal
plug (CN33).

6

(S004)

1

ON

1

2

ON

OFF

(S003)

(S002)

No. 1 unit settings

Unit

No. 1

Outdoor unit

system 1

Unit

No. 1

Outdoor unit

Indoor unit

Remote

controller

Indoor unit

Remote

controller

Inter-unit control wiring

Inter-unit control wiring

Remote controller
communication wiring

Remote controller
cross-over wiring

(S004)

(S003)

(S002)

No. 2 unit settings

System address

(system 1 setting)

System address

(system 2 setting)

No. of indoor units
(6 units setting)

system 2

No. of indoor units

(7 units setting)

•

If link wiring is used

•

If link wiring is used

•

Indoor and outdoor unit power can be turned ON for each system separately.

•

Indoor and outdoor unit power cannot be turned ON for each system separately.

Basic wiring diagram: Example (2)