Simplicity LINC GATEWAY 514067-UAD-A-0509 User Manual
Page 5

514067-UAD-A-0509
Johnson Controls Unitary Products
5
TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor
Default
Min
Max
Point Description
R/W
(2) AV
20
ECO_1ST_STPT
55
40
65
Economizer First Stage Setpoint
R
(5) BV
7
ECONO_INST
–
–
–
Economizer Installed
R
(5) BV
36
ECO_L_TO_SAT
–
–
–
Economizer Loading to Control Supply Air
Temperature Enabled
R/W
(2) AV
19
ECON_MIN_POS
20
0
100
Economizer Minimum Position
R
(5) BV
31
ECONO_STATUS
–
–
–
Economizer Output Status (0=not Free
Cooling, 1= Free Cooling)
R/W
(2) AV
22
ECON_OAEN_SP
27
10
50
Economizer Outside Air Enthalpy Setpoint
R/W
(2) AV
23
ECON_OAT_ENA
55
40
80
Economizer Outside Air Temperature
Enable Setpoint
R/W
(2) AV
84
ECON_RAEN_SP
27
10
50
Economizer Return Air Enthalpy Setpoint
R/W
(2) AV
21
ECO_2ND_STPT
50
40
65
Economizer Second Stage Setpoint
R
(2) AV
41
E_C1_ACM_HRS
–
–
–
Elite Compressor #1 Accumulated Run
Time (in hours)
R
(5) BV
42
E_COMP1_STAT
–
–
–
Elite Compressor #1 Output Status (0=out-
put is OFF, 1=output is ON)
R
(5) BV
45
E_C1_OVRLOAD
–
–
–
Elite Compressor #1 Overload Switch Input
Status (1=closed, 0=open/fault)
R
(2) AV
42
E_C2_ACM_HRS
–
–
–
Elite Compressor #2 Accumulated Run
Time (in hours)
R
(5) BV
46
E_COMP2_STAT
–
–
–
Elite Compressor #2 Output Status (0=out-
put is OFF, 1=output is ON)
R
(5) BV
49
E_C2_OVRLOAD
–
–
–
Elite Compressor #2 Overload Switch Input
Status (1=closed, 0=open/fault)
R
(2) AV
43
E_C3_ACM_HRS
–
–
–
Elite Compressor #3 Accumulated Run
Time (in hours)
R
(5) BV
51
E_COMP3_STAT
–
–
–
Elite Compressor #3 Output Status (0=out-
put is OFF, 1=output is ON)
R
(5) BV
54
E_C3_OVRLOAD
–
–
–
Elite Compressor #3 Overload Switch Input
Status (1=closed, 0=open/fault)
R
(2) AV
44
E_C4_ACM_HRS
–
–
–
Elite Compressor #4 Accumulated Run
Time (in hours)
R
(5) BV
55
E_COMP4_STAT
–
–
–
Elite Compressor #4 Output Status (0=out-
put is OFF, 1=output is ON)
R
(5) BV
58
E_C4_OVRLOAD
–
–
–
Elite Compressor #4 Overload Switch Input
Status (1=closed, 0=open/fault)
R
(5) BV
50
E_CFAN1_STAT
–
–
–
Elite Condenser Fan #1 Output Status
(0=output is OFF, 1=output is ON)
R
(5) BV
59
E_CFAN2_STAT
–
–
–
Elite Condenser Fan #2 Output Status Input
Status (0=output is OFF, 1=output is ON)
R
(5) BV
41
E_FAN_ OVER
–
–
–
Elite Fan Overload Switch Input Status
(1=closed, 0=open/fault)
R
(5) BV
60
E_GAS_VLVE1
–
–
–
Elite Gas Valve #1 Input Status (1=ener-
gized, 0=not energized)
R
(5) BV
62
E_GAS_VLVE2
–
–
–
Elite Gas Valve #2 Input Status (1=ener-
gized, 0=not energized)
R
(5) BV
64
E_GAS_VLVE3
–
–
–
Elite Gas Valve #3 Input Status (1=ener-
gized, 0=not energized)