Simplicity LINC GATEWAY 514067-UAD-A-0509 User Manual
Page 9

514067-UAD-A-0509
Johnson Controls Unitary Products
9
TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor
Default
Min
Max
Point Description
R/W
(2) AV
71
SPCE_ALM_TMP
0
0
25
Space Sensor Alarm Temperature (degrees
F, 0 = disabled)
R/W
(2) AV
72
SPCE_ALM_TIM
0
0
120
Space Sensor Alarm Time (minutes F, 0 =
disabled)
R
(5) BV
26
SEN_FAULT_EN
–
–
–
Space Sensor Fault Override (Construction
Mode) Enabled
R/W
(2) AV
73
SP_OFF_RANGE
3
0
5
Space Temprature Sensor Offset Range
(0-5 degrees)
R
(2) AV
4
SUP_AIR_TEMP
–
–
–
Supply Air Temperature
R/W
(2) AV
70
SAT_ALM_COOL
0
0
80
Supply Air Temperature Alarm Setpoint for
Cooling
R/W
(2) AV
53
SAT_ALM_HEAT
0
0
120
Supply Air Temperature Alarm Setpoint for
Heating
R
(5) BV
22
SAT_COOLING
–
–
–
Supply Air Temperature Limit for Cooling
Enabled
R/W
(2) AV
3
SAT_COOL_SP
50
40
65
Supply Air Temperature Limit for Cooling
Setpoint (degrees F)
R
(5) BV
24
SAT_HEATING
–
–
–
Supply Air Temperature Limit for Heating
Enabled
R/W
(2) AV
52
SAT_HEAT_SP
135
100
180
Supply Air Temperature Limit for Heating
Setpoint (degrees F)
R
(2) AV
34
SFAN_VFD_OUT
–
–
–
Supply Fan VFD Output Status (0-100%)
R
(2) AV
36
ALARM_1
–
–
–
System Alarm #1
R
(2) AV
37
ALARM_2
–
–
–
System Alarm #2
R
(2) AV
38
ALARM_3
–
–
–
System Alarm #3
R
(2) AV
39
ALARM_4
–
–
–
System Alarm #4
R
(2) AV
40
ALARM_5
–
–
–
System Alarm #5
R/W
(2) AV
29
TH_OFFSET
5
1
10
Temperature/Humidity % Humidity that =
1°F of Offset
R/W
(2) AV
26
TEM_HUM_STPT
50
20
80
Temperature/Humidity Setpoint (percent
Humidity)
R
(5) BV
67
FAN_HEAT
–
–
–
Turn OFF Continuous Fan when Starting
Heat Enabled (0=Continuous Fan ON)
R/W
(2) AV
2
UNOC_COOL_SP
85
45
99
Un-Occupied Cooling Setpoint
R/W
(2) AV
51
UNOC_HEAT_SP
60
45
99
Un-Occupied Heating Setpoint
R/W
(2) AV
75
UNOC_OVR_TP
60
0
240
Unoccupied Override Time Period
R/W
(2) AV
65
VAV_CL_LO_SP
55
40
70
VAV Cooling Supply Air Temperature: Lower
Setpoint (degrees F)
R/W
(2) AV
66
VAV_SAT_RSET
72
40
85
VAV Cooling Supply Air Temperature: Reset
Setpoint (Space Temperature)(degrees F)
R/W
(2) AV
64
VAV_CL_HI_SP
60
40
70
VAV Cooling Supply Air Temperature: Upper
Setpoint (degrees F)
R
(5) BV
5
VAV_OCC_HEAT
–
–
–
VAV Occupied Heating Enabled
R/W
(2) AV
60
VAV_OHEAT_SP
68
40
85
VAV Occupied Heating Setpoint (degrees F)