Caution – System Sensor INNOVAIR DH100LP User Manual

Page 6

Advertising
background image

D200-15-00 6 I56-0083-07R

DETECTOR

BOARD

7

6

4

(+) IN

(+) OUT

(+)

(+)

5

8

(–)

(–) IN

(–) OUT

1ST DETECTOR

IN LOOP DH100LP

(–)

RA400Z (OPTIONAL)

REMOTE ALARM LED

2.8 VDC NOM.

IN ALARM

DETECTOR

BOARD

7

6

4

(+) IN

(+) OUT

(+)

(+)

5

8

(–)

(–) IN

(–) OUT

LAST DETECTOR

IN LOOP DH100LP

(–)

RA400Z (OPTIONAL)

REMOTE ALARM LED

2.8 VDC NOM.

IN ALARM

E

O

L

R

STYLE D OPTIONAL WIRING

UL LISTED

COMPATIBLE 2-WIRE

CONTROL PANEL

ALARM

INITIATION

LOOP

(+)

(–)

EOL RESISTOR

SPECIFIED BY

PANEL MANUFACTURER

CAUTION

Do not loop wire under terminals when wiring detectors. Break wire runs to provide system supervision of connections.

1

2

3

4

5

3

4

5

Test +

Test / Reset –

Reset +

Test

Reset

RA +

RA –

DH100LP

RTS451/RTS451KEY

2

1

Alarm

LED

Figure 9. Wiring diagram for the DH100LP to RTS451/RTS451KEY:

Figure 8. System wiring diagram for 2-wire duct smoke detectors (detectors powered from initiating circuit):

A78-2696-00

the duct smoke detector housing, and the LOW side of the
transmitter to the exhaust tube of the duct smoke detec-
tor housing. Measure and record the voltage drop across
the 1000Ω resistor (measurement 2). Subtract the voltage
recorded in measurement 1 from the voltage recorded in
measurement 2. If the difference is greater than 0.15 volts,
there is enough air flow through the duct smoke detector
for proper operation.

Figure 7. Procedure for verifying air flow:

DIFFERENTIAL

PRESSURE

TRANSMITTER

HIGH

LOW

TO SAMPLING TUBE

TO EXHAUST TUBE

VOLT METER

FLUKE MODEL 87

OR EQUIVALENT

1000 OHM 5% 1 WATT RESISTOR

9 VOLT

BATTERY

9 VOLT

BATTERY

9 VOLT

BATTERY

15 TO 36VDC

SUPPLY

[6.1.5] Filter Replacement
The filters do not substantially affect smoke performance
even when up to 90% of the filter is clogged. Quarterly
visual inspection usually suffices to determine whether the
filters should be replaced because only a high percentage
of contamination affects performance. If further testing is
required, compare differential pressure readings with and
without the filters installed. If the difference exceeds 10%
replace the filters. In no case should the pressure differen-
tial fall below 0.0015 inches of water.

[6.2] Standby, Alarm, And Sensitivity Tests
[6.2.1] Standby And Trouble
Standby — Look for the presence of the flashing green

LED through the transparent housing cover.
The LED should flash approximately every 10
seconds.

Trouble — If the Green LED does not flash, then the de-

tector lacks power (check wiring, panel, or
power supply), the detector board is missing
(replace), or the unit is defective (return for
replacement).

A78-2697-00