[9] Model DH100LP Air Duct Smoke Detector Specifications

Operating Temperature: +32° to +131° F 0° to +55° C
Storage Temperature: –22° to +158° F –30° to +70° C
Humidity: 10% to 93% R.H. noncondensing
Air Velocity: 100 to 4000 ft./min. 0.5 to 20.3 m/sec.
Dimensions: 14.38” L x 5.5” W x 2.75” D 36.5cm L x 14cm W x 7cm D

Weight: 3.25 pounds 1.5 kg
Electrical Ratings — includes base and detector
System Voltage: 12/24 VDC
Maximum Ripple Voltage: 4 Volts peak to peak
Start-up Capacitance: 0.02 µF maximum
Standby Ratings: 8.5 VDC minimum
35 VDC maximum
120 µA maximum
Alarm Ratings: 4.2 VDC minimum at 10mA
6.6 VDC maximum at 130mA
Alarm current must be limited to 130mA or less by the control panel.
If used, the RA400Z remote lamp operates within the specified alarm currents.
Reset Voltage: 2.50 VDC minimum
Reset Time: 0.3 Sec. maximum
Start-up Time: 34.0 Sec. maximum

Three-Year Limited Warranty

System Sensor warrants its enclosed air duct smoke detector to be free
from defects in materials and workmanship under normal use and ser-
vice for a period of three years from date of manufacture. System Sensor
makes no other express warranty for this air duct smoke detector. No
agent, representative, dealer, or employee of the Company has the author-
ity to increase or alter the obligations or limitations of this Warranty. The
Company’s obligation of this Warranty shall be limited to the repair or
replacement of any part of the air duct smoke detector which is found to
be defective in materials or workmanship under normal use and service
during the three year period commencing with the date of manufacture.
After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672)
for a Return Authorization number, send defective units postage prepaid
to: System Sensor, Returns Department, RA #__________, 3825 Ohio

Avenue, St. Charles, IL 60174. Please include a note describing the mal-
function and suspected cause of failure. The Company shall not be obli-
gated to repair or replace units which are found to be defective because
of damage, unreasonable use, modifications, or alterations occurring
after the date of manufacture. In no case shall the Company be liable for
any consequential or incidental damages for breach of this or any other
Warranty, expressed or implied whatsoever, even if the loss or damage is
caused by the Company’s negligence or fault. Some states do not allow
the exclusion or limitation of incidental or consequential damages, so the
above limitation or exclusion may not apply to you. This Warranty gives
you specific legal rights, and you may also have other rights which vary
from state to state.