2050/2060 Gas Monitors (5/04)

Page:

Instruction Manual

4

3.0 OPERATION

3.1 Introduction

Under normal conditions the gas sensor module does
not require operator or technician intervention. The
following are conditions under which the module re-
quires attention:
- Routine periodic calibration
- Sensor replacement on a planned schedule

or when a sensor failure occurs.

- Periodic cleaning as necessary.

3.2 Alarms

Three alarm conditions are possible. These can be
detected visually at the optional Sierra Monitor con-
troller and at the module.

Warm-Up Alarm

Oscillating (On/Off) contact closure and “red/
green” visual indication when power is first con-
nected to the module, followed by a continuous
closure of approximately 2-60 minutes indicat-
ing warm-up.

Buzzer

Relay

Relay
Fail Safe

On/Off

Oscilating

Oscilating

Gas Alarm

Sustained contact closure and solid red light
(once the warm-up time is completed) indicat-
ing the presence of gas at, or above, the pre-set
alarm limit.
Table 2.1

Buzzer

Relay

Relay
Fail Safe

On

Closed

Open

Trouble Alarm

Interrupted contact closure and “red/green” vi-
sual indication (once the warm-up time is com-
pleted) after unit has been in operation, indicat-
ing either a failed sensor or calibration problems.

Buzzer

Relay

Relay
Fail Safe

On/Off

Oscilating

Oscilating

3.3 Outputs

For the non-relay configurations a 5 volt DC TTL
signal is provided to activate remote alarms such
as the Sierra Monitor Alarm Panels. Relay configu-
ration alarm conditions described above are trans-
mitted to the annunciator as relay contact closures
from the monitor.

The alarm outputs are non-latching closed contacts.
As soon as the gas concentration falls below the
alarm set-point, the alarm will stop and the alarm
output will cause the relay to de-energize and the
contacts will open.

During warm-up and failed sensor alarms the re-
lays contact and the display LED's oscillate at ap-
proximately one hertz.

=