Available options, Wh w – SPX Cooling Technologies Marley QuadraFlow User Manual

Page 7

Advertising
background image

Inlet Water Bypass—provision for total water bypass directly into the tower collection basin during cold

weather operation.

Hoistable Steel Grillage—allows assembling tower at grade on temporary supports and hoisting

into final location.

Fire Retardant FRP—flame spread rating of 25 or less per ASTM E-84.

Control Systems—ranging in sophistication from standard fan starters and disconnects to

Programmable Logic Controllers that work in conjunction with your building or process system.

Variable Speed Drive—the ultimate in temperature control, energy management, and

mechanical equipment longevity

Electric Basin Heater Package—maintains collection basin water temperatures between 4°C

and 7°C during tower shutdown.

Vibration Limit Switch—shuts down the fan motor if excessive vibration occurs.

Solid State Water Level Control Package—monitor basin water level with solenoid-valve water

makeup. Configurations include makeup along with high and low water level alarm and cutoff

and electric basin heater cutoff.

Magnetrol

®

Electric Float Switch—monitor basin water level with solenoid-valve water makeup.

/ Available Options /

W

H

W

TOWER MODELS

TONS

W

H

21120

129-183

3861

2184

21220

186-211

3861

2565

21320

204-256

3861

2972

22120

243-304

4293

2591

22220

312-425

4293

3023

23120

390-475

5080

3023

23220

419-546

5080

3429

24120*

531-836

7468

3886

24220*

796-1047

7468

4902

*Models in this box size require a taller fan cylinder