Output circuits, Notification appliance circuits, T b 2 – System Sensor PDRP-1001 Series User Manual

Page 20

Advertising
background image

2. Installation

Output Circuits

20

PDRP-1001 Instruction Manual PN 50734:D0 04/06/01

Output Circuits

Notification Appliance Circuits

The control panel provides two Style Z (Class A) or Style Y (Class B) Notification Appliance Circuits,
which are supervised and power-limited.

Each circuit is capable of 1.5 amps of current. Total current drawn from both NACs and both Releasing
Circuits (see "Releasing Circuits" on page 21) cannot exceed 2.25 amps.

Note: Refer to the "Appendix B: Compatible Devices" on page 39 for suitable devices.

• For DIP switch configuration, see "Setting Mode of Operation" on page 28.

• For non-silenceable service on NAC#1, see "Non-Silenceable Service" on page 34.

• Unused circuits must be connected with a dummy load as shown.

Figure 9 Notification Appliance Circuits

T B 2

MR

P

44-

nac.cdr

Polarized
Horn

Polarized
Strobe

Polarized
Bell

Style Z

(Class A)

4.7K, 1/2-Watt ELR
PN 71252 (UL listed)

Unused Style Y Circuit

4.7K, 1/4-Watt ELR

PN 71252 (UL listed)

Style Y

(Class B)

Advertising