Optional Modules

Overview

The control panel has two module connectors - J5 (upper position) and J8 (lower position). Three modules
are available for the panel and they can be used in any combination, including duplicate modules. The
corresponding option jumper must be cut before installation of an optional module, to enable module
supervision.

• The 4XZM Zone Relay and the 4XTM Transmitter Modules can be installed in either position.

• The 4XLM Interface Module must be installed in the lower position only.

Installation - Upper Position

To install either the 4XZM or 4XTM module in the upper position follow these instructions:

Figure 13 Module Installation - Upper Position

Step

Action

1

Cut jumper ‘OPT1’ on main circuit board.

2

Insert the two stand-offs into the holes located on the right-side edge of the
main board. Secure with nuts and tighten securely.

3

Align the pins of J5 (and J4) connectors on the main board with the holes on
the underside of the J2 (and J1) connector on the optional board. Carefully
press down on the optional board until the pins are through the connectors
and it rests on the stand-offs.

4

Secure optional board to stand-offs with screws. Tighten securely.

5

Affix the terminal identification label (provided with the module) on the
back surface of the backbox, aligning it with the terminals on the module.