Sierra Monitor Corporation HRG015-W User Manual

Page 60

Advertising
background image

HRX-OM-J049-A
Chapter 7 Documents

7.1 Standard Specifications

HRG010-W HRG015-W

1st edition : Aug. 2006

Rev. A: May. 2007

7-2

Table 7-1 Standard Specifications (2/2)

Item

HRG010-W

HRG015-W

ALARM1

System stop function for low tank level (tank level switch),

pump/compressor reverse rotation detection (phase relay)

Protection against refrigerant pressure rise

(with a high pressure cutoff SW configured to control pressure to 3.0MPa)

ALARM2

System stop function for pump overload (overcurrent relay), system stop function for abnormal

circulating fluid temperature rise (set temp. of the temperature controller: 43°C)

ALARM3

System stop function for compressor overload (overcurrent relay)

P

rot

ect
iv

e f

unc
tion

(f

or equi

pm
ent
)

Emergency

stop

Others

Protection against supply pressure rise (with a manual relief valve), Antifreezing temperature

control (with an auto pump opera on temperature controller)

External panel

SGCC (Munsell 10Y8/0.5 Urban white)

Operation panel

SGCC (DIC183 Blue)

Base

SECC (Munsell 10Y6/0.5 Urban gray)

Wetted part

SUS (tank, pump impeller, circulating fluid

IN/OUT), BC (pump casing, hose fitting), PVC

Nylon 12, Synthetic rubber (pipe hose),

Polyurethane (limnimeter)

SUS (tank, circulating fluid IN/OUT), BC (pump
impeller, pump casing, hose fitting), PVC Nylon

12, Synthetic rubber (pipe hose), Polyurethane

(limnimeter)

Internal piping for

refrigerant

C1220T

Refrigerant used

R407C (HFC)

M

at

eri

al

/S

ubst

anc
e

Refrigerant supplied

amount

1400±20g 1700±20g

Eye bolt M12

× 4 pcs., Y-shaped strainer Rc1/2 ×

1 pcs., nipple for strainer piping 1/2

× 1 pcs

Eye bolt M12

× 4 pcs., Y-shaped strainer Rc3/4

× 1 pcs., nipple for strainer piping 3/4 × 1 pcs

Accessories

(A power supply, signal cable and connection terminal must be prepared under your responsibility.)

Weight 200kg

220kg