Chapter 4. WIRING

4-6

4-5

Connecting the Ground and Power Supply

■

Power supply

Connect the DCP301 to a single-phase power supply for controllers, and take measures
to prevent the influence of electrical noise.

1

3

2

1

2

E

3

4

GND

~

Instrument
power supply

Other circuits

GND

GND

Recommended

line filter

81446364-001

DCP301

200/200V,

100/100V

insulated transformer

• If the power supply generates a lot of electrical noise, we recommend inserting

an insulating transformer in the power circuit and using a line filter.

Recommended line filter: Model No. 81446364-001

• After providing anti-noise measures, do not bundle primary and secondary power

leads together, or pass them through the same piping or wiring duct.

■

Ground

When it is difficult to ground shielded cable, prepare a separate ground terminal (earth
bar).

Ground type: 100

Ω

max.

Ground cable: 2mm sq. min soft-copper wire (AWG14)
Cable length: Max. 20m

3

FG
terminal

DCP301

GND terminal plate

GND (100

Ω

max.)

Shielded cable

Use only the FG terminal (3) on the DCP301 for grounding. Do not ground across
other terminals.

Handling Precautions

Handling Precautions