Chapter 4. WIRING

4-9

WARNING

4-8

Connecting control outputs (outputs 1, 2)

Before wiring, or removing/mounting the DCP301, be sure to turn the power
OFF. Failure to do so might cause electric shock.

■

Relay output (0D)

Connect as follows.

11

12

13

Load

Power supply

Contact rating, resistive load
5A (30Vdc/120Vac)
4A (240Vac)

Minimum switching current: 100mA

When switching small currents, connect a bleeder resistor to allow current flow of
the minimum relay switching input (100mA min.).

■

Current output (5G)

Connect as follows.

11

12

13

Actuator

4 to 20/0 to 20mAdc
Resistive load 600

Ω

max.

11

12

13

14

15

16

G

T

Y

1

3

2

Open side

Power supply

Closed side

Open

Closed

Contact rating
4A (120Vac, cosø=0.4)
2A (240Vac, cosø=0.4)

Feedback resistance
100 to 2500

Ω

Load

Load

• The life of internal relays is limited.

Avoid setting the PID constant in such a way that results in excessive repeated
ON/OFF switching.

• When using a 100/200Vac motor, pay attention to rush current and the contact

rating. If necessary, provide an external auxiliary relay.

• Separate the wiring for motor terminals (11) (12) (13) and feedback resistor

terminals (14) (15) (16).
(Do not wire the leads in the same duct or use 6-core cable. Doing so might
result in faulty controller operation caused by electrical noise when the motor is
started up.)

• When controlling without motor feedback with variable parameter

M

.-C

set to

“2”, terminals (14) (15) (16) need not be connected.

4 to 20mAdc and 0 to 20mAdc can be selected in setup data

C

9

0

.

■

Position-proportional output (2G)

Connect as follows paying attention to the switching direction.

Handling Precautions

Handling Precautions

Handling Precautions

Advertising