Table 5 - Category I Horizontal Venting Requirements - Standard Combustion

Vent

Maximum Number

Maximum Horizontal

Minimum

Extension

Unit

Diameter

Elbows

Vent Length

Vertical Rise

Distance

Size

(in)

*

(Ft.)

(In.)

from

Wall

(In.)

30

4 1 5 8 36

4 2 10 18 36

45

4 1 10 24 36

4 1 15 24 36

4 2 5 24

36

60

4 2 10 18 36

75

5 2 7 24

36

90

5 2 7 24

24

105

5 2 7 24

24

120

5 1 5 24

24

5 2 7 24

24

*One elbow is required to make the vertical extension, See Figure 13.

Figure 13 - Category I Horizontal Venting Requirements