Figure 10. multiple fan shutdown (interconnect), Wire wiring to apa451 – System Sensor INNOVAIR DH100ACDCP User Manual

Page 6

Advertising
background image

D100-68-00 6 I56-1147-12R

24V

120

VAC

220/240

VAC

9

10

A

B

C

AVAILABLE POWER INPUTS

ALARM AUXILIARY CONTACTS

FOR FAN SHUTDOWN, ETC.

16

6

17

7

18

8

N.C.

C.

N.O.

N.O.

C.

N.C.

ALARM AUXILIARY CONTACTS SHOWN IN

STANDBY. CONTACTS TRANSFER DURING

ALARM AS INDICATED BY THE ARROWS.

SUPERVISORY TROUBLE CONTACTS

TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY.

CONTACTS OPEN WHILE DETECTOR PCB OR POWER IS

REMOVED OR WHEN TAMPER FEATURE TIMES OUT. OPEN

CONTACTS SIGNAL TROUBLE CONDITION TO PANEL.

24V

220/240

VAC

9

10

A

B

C

AVAILABLE POWER INPUTS

ALARM AUXILIARY CONTACTS

FOR FAN SHUTDOWN, ETC.

16

6

17

7

18

8

N.C.

C.

N.O.

N.O.

C.

N.C.

ALARM AUXILIARY CONTACTS SHOWN IN

STANDBY. CONTACTS TRANSFER DURING

ALARM AS INDICATED BY THE ARROWS.

SUPERVISORY TROUBLE CONTACTS

TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY.

CONTACTS OPEN WHILE DETECTOR PCB OR POWER IS

REMOVED OR WHEN TAMPER FEATURE TIMES OUT. OPEN

CONTACTS SIGNAL TROUBLE CONDITION TO PANEL.

14

3

3

14

4

5

ALARM

INITIATION

CONTACTS

CONTACTS SHOWN

OPEN IN STANDBY.

CONTACTS CLOSE

IN ALARM.

4

5

ALARM

INITIATION

CONTACTS

CONTACTS SHOWN

OPEN IN STANDBY.

CONTACTS CLOSE

IN ALARM.

ALARM

INITIATION

LOOP

UL LISTED 4-WIRE

CONTROL PANEL

FIRST DETECTOR IN THE LOOP

DH100ACDCP

LAST DETECTOR IN THE LOOP

DH100ACDCP

EOL RESISTOR

SPECIFIED BY

PANEL MANUFACTURER

CONNECT POWER SOURCE

TO APPROPRIATE TERMINALS

OF EACH DETECTOR. SEE

SPECIFICATIONS FOR

ADDITIONAL POWER SUPPLY

INFORMATION.

FOR WIRING OF AUXILIARY

DEVICES, REFER TO

MANUFACTURER'S

INSTALLATION INSTRUCTIONS

OR CONTACT MANUFACTURER.

NOTE: THE SUPERVISORY RELAY NOW

PROVIDES A "FORM C" CONTACT FOR

CUSTOMIZED APPLICATIONS.

FOR STANDARD APPLICATIONS, ONLY

THE "NO" CONTACT IS USED

POWER INPUTS ACCEPT

24 VDC, 24 VAC 50-60 HZ,

120 VAC 50-60 HZ, OR

220/240 VAC 50-60 HZ.

CONNECT POWER SOURCE

TO APPROPRIATE TERMINALS

OF EACH DETECTOR.

AUX. CONTACT RATINGS

10A @ 30 VDC RESISTIVE

10A @ 250 VAC

100mA MINIMUM @ 5 VDC

NOT INTENDED FOR

CONNECTION TO CONTROL

PANELS.

TROUBLE CONTACT RATING

2.0 A @ 30 VDC resistive

2.0 A @ 125 VAC resistive

+

120

VAC

CAUTION

Do not loop wire under terminals when wiring detectors. Break wire runs to provide system supervision of connections.

Figure 8. Wiring diagram for DH100ACDCP to APA451:

A78-2352-27

Figure 7. System wiring diagram for 4-wire duct smoke detectors:

��

��

��

��

������������

������������

����������

��������

������������

������ �������������������������������������������������

�������������������������������������������������������

�����

���������

�����

�����������
������

4-Wire Wiring to APA451

������

����������

Figure 9. Wiring diagram for DH100ACDCP to
RTS451KEY and interconnect feature:

15

19

14

3

20

2

11

2

6

1

Alarm Signal

Aux. Power +

Sup. N. O.

Sup. COM

Aux. Power –

Reset

Test

(Red LED) Alarm

(Green LED)
Power

DH100ACDCP

RTS451/RTS451KEY

5

4

3

*

For RTS451KEY
only without a
control panel.

*

Important Interconnect Notes
• When using the interconnect feature, all in-
terconnected units must be powered with
the same, independent supply.
• Polarity must be maintained throughout the
interconnect wiring. Connect terminal 12 on
unit 1 to terminal 12 on unit 2 and so on.
Similarly, connect terminal 1 on unit 1 to ter-
minal 1 on unit 2 and so on.

Figure 10. Multiple fan shutdown (interconnect):

1

6

12

16

A

B

C

FAN

CONTROL

SYSTEM

CONTROL

POWER OR

THERMOSTAT

1

6

12

16

A

B

FAN

CONTROL

SYSTEM

CONTROL

POWER OR

THERMOSTAT

DETECTOR 1

C

DETECTOR 2

1

6

12

16

A

B

FAN

CONTROL

SYSTEM

CONTROL

POWER OR

THERMOSTAT

C

DETECTOR 3

1

12

+

NEXT

DETECTOR

Advertising