15.3 Protective Function Table

The following table shows functions and operations which activate to protect the UPS.
The ○ mark indicates lit LEDs and buzzer alarms.

Operation panel (front panel) indicators

Alarms

Item

INPUT

Green

OUTPUT

Green

INV.ON

STAND

BY

Green

ALARM

Red

O.L
Red

BATT.

LOW

Red

Buzzer

pattern

(*1)

Protective

functions

(UPS operations)

Notes

Preparation

○

(*2) (*2) -

-

-

-

Rectifier, charger,
operation

Power up

Normal

○

○

○

-

-

-

-

Inverter, charger
operation

Power up,
operation

Serious

failure

○

○

Blink

○

Blink

○

-

-

○

(1)

Stop inverter

Bypass supply

Overload

(effective

value)

○

○

Blink

○

Blink

-

○

-

○

(4)

Auto return

Forced
bypass

○

○

Blink

○

Blink

-

-

-

-

Bypass supply
Charger operation

Manual switch
to bypass supply

Input over

voltage

○

Blink

○

○

-

-

-

○

(2)

Battery
operation

Input over

voltage

(prolonged)

○

Blink

○

○

-

-

○

○

(3)

Battery
operation (*3)

Power

outage

○

Blink

○

○

-

-

-

○

(2)

Battery

operation

Power

outage

(prolonged)

○

Blink

○

○

-

-

○

○

(3)

Battery

operation (*3)

Input error
(frequency)

○

Blink

○

○

-

-

-

○

(2)

Battery
operation

Input error
(prolonged)

○

Blink

○

○

-

-

○

○

(3)

Stop rectifier and
charger

Continue inverter
supply.

Battery

operation (*3)

Battery

failure

○

○

Blink

○

Blink

○

-

○

○

(1)

Stop inverter

Bypass supply

(*1): Press

on the front panel of the UPS to stop the buzzer. If a failure occurs, contact

your supplier or Sanyo Denki representative as soon as possible.
Buzzer sound patterns:
(1) *

Continuous tone

(2) **......**......
(3) **********...... Continuous beeps
(4) ****......****...

(*2): In this state, the LED blinks or is off, depending on the setting of item ⑪ “Inverter stop

operation”" in §10.1 “Setup Menu Item List”.

When

item

⑪

is set to “Bypass”: ○ Blinks

When

item

⑪

is set to “OFF”: -

(*3): Battery operation. Stops inverter operation when final battery discharge is reached.