Troubleshooting the millivolt gas control system – Superior NMC-LCDC User Manual

Page 16

Advertising
background image

16

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

TROUBLESHOOTING THE MILLIVOLT GAS CONTROL SYSTEM

1. Spark ignitor will not light

pilot after repeated
triggering of ignitor button.

2. Pilot will not stay lit after

carefully following the
lighting instructions.

3. Pilot burning, no gas to

burner, Valve knob “ON,”
Wall Switch “ON.”

4. Frequent pilot/burner outage

problem.

CORRECTIVE ACTION

SYMPTOM

A. Defective ignitor

(no spark at electrode).

B. Defective or misaligned electrode

at pilot (spark at electrode).

C. Gas supply pressure errant.

D. Pilot orifice plugged.

A. Defective pilot generator
(thermocouple).

A. Wall switch or wires defective.

B. Thermopile may not be generating

sufficient millivoltage.

C. Plugged burner orifice.

A. Pilot flame may be too low or

blowing (high) causing the pilot/
valve safety to drop out.

Check for spark at electrode and pilot; if no spark and
electrode wire is properly connected, replace ignitor.

POSSIBLE CAUSES

N

ote: Before troubleshooting, make sure that the appliance main line gas shut-off valve and the gas control valve are in the "OPEN"

position and the burner ON/OFF switch is in the “ON” position.

Important: Valve system troubleshooting should only be accomplished by a qualified service technician.

Clean and/or adjust pilot flame for maximum flame impinge-
ment on thermocouple

(Figure 9 on page 7).

Check burner orifice for stoppage and remove.

Check thermopile with millivolt meter. Take reading at thermo-
pile terminals of gas valve. Should read 325 millivolts mini-
mum with optional wall switch “OFF.” Replace faulty thermo-
pile if reading is below specified minimum.

Check wall switch and wires for proper connections. Jumper
wire across terminals at wall switch, if burner comes on,
replace defective wall switch. If okay, jumper wires across wall
switch wires at valve, if burner comes on, wires are faulty or
connections are bad.

Check pilot flame, it must impinge on thermocouple

(Figure

9 on page 7) Clean and/or adjust pilot for maximum flame
impingement on thermocouple. Ensure that the connection
between the valve and thermocouple are tight and secure.

Clean or replace pilot orifice.

Check inlet gas pressure. It should be within the limits as
marked on the rating plate.

Using a match, light pilot. If pilot lights, turn off pilot and
trigger the ignitor button again. If pilot lights, an improper gas
mixture caused the bad lighting and a longer purge period is
recommended. If pilot will not light – check gap at electrode
and pilot – should be

¹⁄₈" to have a strong spark. If gap

measures

¹⁄₈", replace pilot (Figure 9 on page 7).

Advertising
This manual is related to the following products: