Steam connections (steam drying tumblers) – Speed Queen Drying Tumblers SCB50EG User Manual

Page 50

Advertising
background image

48

M412616

STEAM CONNECTIONS (Steam Drying Tumblers)

Figure 24

Figure 25

TUMBLER

MODEL

STEAM PRESSURE

(PSI)

MINIMUM

PIPE DIAMETER

STEAM TRAP SIZE

(Pounds Condensate/Hour)

30CSL

7-15

3/4" (1.9 cm)

140

30 CSH

80-100

3/4" (1.9 cm)

140

50 CSL

7-15

3/4" (1.9 cm)

140

50 CSH

80-100

3/4" (1.9 cm)

160

75 CSL

7-15

3/4" (1.9 cm)

140

75 CSH

80-100

3/4" (1.9 cm)

160

STEAM

BONNET

SUPPLY

RETURN

GATE

VALVE

TRAP WITH

BUILT-IN

STRAINER

UNION

CHECK

VALVE

CHECK

VALVE

CONDENSATE

RETURN LINE

FROM

SUPPLY LINE

OPTIONAL

VACUUM

BREAKER

SOLENOID

VALVE

(Supplied with

machine)

NOTE: See Figure 25 for sizing
of steam lines. Piping must
also be sized accordingly for
length of runs, and number
of elbows.

RELIEF

VALVE

30.5 cm (12")

RISERS

T262IE3A

Advertising