Operating procedures, 1 ups startup (normal operation), Press and hold – Sanyo SANUPS E11A102A User Manual

Page 22: For one second, Set main sw on the back panel of the ups to “on

Advertising
background image

− 19 −

EXT.
BATT

MAIN SW

9. Operating Procedures

9.1 UPS Startup (Normal Operation)





Check that the INPUT indicator has

changed from blinking to lit, and then
proceed to step ②.




・

The green LOADLEVEL 25 to 100% indicators and the red LOADLEVEL O.L indicator light

according to the load connected to the UPS.

・

The green ECONOMY indicator lights when the UPS operating mode is Economy Mode.

・

The green DOUBLE CONVERSION indicator when the UPS operating mode is Double
Conversion Mode.

・

When the green DOUBLE CONVERSION indicator and the green ECONOMY indicator are both
off, the UPS is in Active Filter Mode.

This manual uses a frame to indicate switches. (Example: INV.ON/STAND BY ).
It also describes the color of the LED whenever it refers to an indicator on the control panel.
(Examples: Green INV.ON/STAND BY, red ALARM)

Hold for 1 second.

Buzzer

Musical trill

LEDs

Green INPUT

Lit

Green INV.ON/STAND BY Lit

Green OUTPUT

Lit

②

Press and hold

for one second.

①

Set MAIN SW on the back panel of the UPS to “ON”.

LEDs

Green INPUT

Blinking

Green INV.ON/STAND BY

Off

Green OUTPUT

Off

↓

Green INPUT

Lit

Green INV.ON/STAND BY Off

Green OUTPUT

Off

①

Set to “ON”.

Indicates a lit LED

In the illustrations in this manual

Indicates a blinking LED