Lennox Hearth Direct Vent MPD-40 Series User Manual

Page 20

Advertising
background image

20

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

V

H

H1

V1

**Wall Firestop/Spacer

(SV4.5HF)

*Ceiling

Firestop/Spacer

(SV4.5VF)

*When using Secure Flex,

use Firestop/Spacer

SF4.5VF

**When using Secure

Flex, use Firestop/Spacer

SF4.5HF

**Wall Firestop/Spacer

(SV4.5HF)

V

H2

H1

H

**Wall Firestop/Spacer

(SV4.5HF)

*Ceiling

Firestop/Spacer

(SV4.5VF)

*When using Secure Flex,

use Firestop/Spacer

SF4.5VF

**When using Secure

Flex, use Firestop/Spacer

SF4.5HF

H Maximum

V Minimum

feet

feet

feet

5

(1.524)

2

(0.610)

1

(0.305)

10

(3.048)

4

(1.219)

2

(0.610)

15

(4.572)

6

(1.829)

3

(0.914)

20

(6.096)

8

(2.438)

4

(1.219)

V + H + H1 + H2 = 40 feet (12.2 m) Max.

H = 8 feet (2.438 meters) Max.

H + H1+ H2 = 20 feet (6.096 meters) Max.

H

+ H

1

+ H

2

Maximum

TABLE K

(meters)

(meters)

(meters)

Example: If 20 feet of (H) horizontal vent
run is needed, then 4 feet minimum of (V)
vertical vent will be required.

This table shows a 1 (V) to 5 (H) ratio. For
every 1 foot of (V) vertical, you are allowed
5 feet of (H) horizontal run, up to a maxi-
mum horizontal run of 20 feet.

An elbow is acceptable as 1 foot of vertical
rise except where an elbow is the only
vertical component in the system. See
Figure 35.

V Minimum

feet

feet

5

(1.524)

Elbow Only

5

(1.524)

1

(0.305)

10

(3.048)

2

(0.610)

15

(4.572)

3

(0.914)

20

(6.096)

4

(1.219)

(meters)

TABLE L

(meters)

H Maximum

1

1

H

+ H

1

= 20 feet (6.096 m) Max.

V

+ V +

H

+ H = 40 ft. (12.192 m) Max.

Figure 40

- Top Vent - THREE 90 DEGREE ELBOWS

Figure 39

- Rear Vent - THREE 90 DEGREE ELBOWS (Square termination SV4.5HT-2 shown.)

See

Table 4 on page 18 as an aid in venting component selection for a particular range of exterior wall thicknesses.

See

Table 4 on page 18 as an aid in venting component selection for a particular range

of exterior wall thicknesses.

Example: If 20 feet of (H) horizontal vent run is
needed, then 4 feet minimum of (V) vertical vent
will be required.

This table shows a 1 (V) to 5 (H) ratio. For every
1 foot of (V) vertical, you are allowed 5 feet of (H)
horizontal run, up to a maximum horizontal run
of 20 feet.

(Square termination
SV4.5HT-2 shown.)

HORIZONTAL VENT FIGURES/TABLES (continued)