Communication Interfaces

91

Table 15 shows the various groups, the settings contained within and the type of value it requires.
Table 15

Group settings and values

Group

Item:

Description

Value Type

Value Notes

Group 1:

System

Ratings

1

Input Volts (PDU)

Integer

Set per system spec.

2

Volts

Integer

Set per system spec.

3

Current

Integer

Set per system spec.

4

Frequency

Scaled

Desired freq. x 10 (600 = 60 Hz)

Group 2:

System

Settings

1

Language

Enumeration [Not supported at this time]

2

System Model Number

String

14 Character max.

3

System ID Number

String

8 Character max.

4

System Tag Number

String

8 Character max.

5

System Order Number

String

8 Character max.

6

Options_1

Bitpacked

14 Character max.

7

Autodial Primary Line

String

20 Character max.

8

Autodial Secondary Line

String

20 Character max.

9

Autodial Pager Number

String

20 Character max.

10

Autodial Pager PIN

String

10 Character max.

11

Modem Init String

String

20 Character max.

12

Modem Baud Rate

Enumeration 0 = 2400, 1 = 9600, & 2 = 19200 bps

13

Modem LGS Check - Day

Bitpacked

14

Modem LGS Check - Time

Bitpacked

15

Comms Options 1

Bitpacked

See section 12.1.3.

16

Comms Options 2

Bitpacked

See section 12.1.3.

Group 3:

User

Settings

1

SRC1 Fast Undervoltage Setpoint

Integer

In % of nominal below nominal

2

SRC1 Slow Undervoltage Setpoint

Integer

In % of nominal below nominal

3

SRC1 Slow Undervoltage Detect Delay Integer

In number of lines cycles

4

SRC1 Overvoltage Setpoint

Integer

In % of nominal above nominal

5

SRC1 Overvoltage Detect Delay

Integer

In 1/4 lines cycles

6

SRC1 I peak Transfer Setpoint

Integer

x 10

7

SRC2 Fast Undervoltage Setpoint

Integer

In % of nominal below nominal

8

SRC2 Slow Undervoltage Setpoint

Integer

In % of nominal below nominal

9

SRC2 Slow Undervoltage Detect Delay Integer

In number of lines cycles

10

SRC2 Overvoltage Setpoint

Integer

In % of nominal above nominal

11

SRC2 Overvoltage Detect Delay

Integer

In 1/4 lines cycles

12

SRC2 I peak Transfer Setpoint

Integer

x 10

13

Max. Transfer Phase Angle

Integer

In degrees

14

Output Frequency Deviation

Integer

Freq. in Hz x 10

15

ReTransfer Delay Time

Integer

In seconds

16

Horn Volume

Integer

Range: 1-10

17

Critical Option Enabling

Bitpacked

See section 12.1.3.

18

Non-Critical Option Enabling

Bitpacked

See section 12.1.3.

Group 4:

Event

Mask

Settings

1 to 63

Event Mask settings for faults

Event Mask

See section 12.1.3.

64 to 143 Event Mask settings for alarms

Event Mask

See section 12.1.3.