Monitoring system, Rack monitoring system, Ppendices – Lindy Carbon Monoxide Alarm User Manual
Page 51

A
PPENDICES
A
PPENDICES
51
Monitoring System
Rack Monitoring System
Objects under
digitalInTable
(1.3.6.1.4.1.1909.10.2.1)
for example:
number of changes of input 9:
1.3.6.1.4.1.1909.10.2.1.1.5.9
Objects under
alertInTable
(1.3.6.1.4.1.1909.10.2.2)
for example :
Reset sensors on Alert In 2
1.3.6.1.4.1.1909.10.2.2.1.3.2 := 1
Object under ups I
N
T
ABLE
(1.3.6.1.4.1.1909.10.2.3)
Variable Type
Value
Access
1 digitalInEntry
1 digitalInIndex
INT RO
2 digitalInDescr
DS RW
3 digitalInState
INT
{ off (1), on (2)} RO
4 digitalInLastChange
TT RO
5 digitalInChanges
CNT RO
Variable
Type
Value
Access
1 alertInEntry
1 alertInIndex
INT
RO
2 alertInDescr
DS
RW
3 alertInState
INT
{off (1), on (2)} RO
4 alertInLastChange
TT
RO
5 alertInChanges
CNT
RO
6 alertInReset
INT
{default (1)
RW
alertIn-reset (2)}
Variable Type
Value
Access
1 upsInEntry
1 upsInIndex
INT
RO
2 upsInDescr
DS
RW
3 upsInState
INT
{off (1), on (2)} RO
4 upsInLastChange
TT
RO
5 upsInChanges
CNT RO