REFER TO SL-16655, LIEBERT XTREME DENSITY SYSTEM DESIGN MANUAL, AND SL-16674, LIEBERT XDC USER MANUAL FOR ADDITIONAL DETAIL.

DPN001599

REV 12/11
REV 4

LIEBERT XD CHILLER (XDC) WITH iCOM CONTROLS

PAGE 6/6

NOTES:

1. CONTROL WIRING MUST BE CLASS 2 AND INSTALLED IN
ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC).

2. REQUIRES SHIELDED CABLE.

K11COM

COMMON WARNING OUTPUT

K11NO

K11NC

K11

TO REMOTE ALARM

CIRCUIT BY OTHERS

K11

N.O. CONTACT BY OTHERS

FOR INDICATION OF ALARM, WIRE
N.O. CONTACTS FROM REMOTE
ALARM DEVICE AS SHOWN.

24

50

INPUT: REMOTE ALARM DEVICE

N.O. CONTACTS REQUIRED

54

24

ALARM WHEN CLOSED.

INPUT: FAN BREAKER STATUS

N.O. CONTACTS REQUIRED

51

24

ALARM WHEN CLOSED.

INPUT: CONDENSATION

DETECTION

FOR SHUTDOWN OF CONTROL
CIRCUIT, REMOVE JUMPER
BETWEEN TERMINALS 37 & 38
AND REPLACE WITH N.C. CONTACT

38

37

INPUT: REMOTE SHUTDOWN

N.C. CONTACTS BY OTHERS

K3COM

COMMON ALARM OUTPUT

K3NO

K3NC

K3

TO REMOTE ALARM

CIRCUIT BY OTHERS

FOR CONTACTS INDICATING AN
ALARM CONDITION.
(MAX) 1.0AMP @ 24V

K3

FOR CONTACTS INDICATING AN
ALARM CONDITION.
(MAX) 1.0AMP @ 24V

FACTORY WIRED
TEMPERATURE SENSOR.

1

1

2

1

Liebert XDC Extra Low Voltage field connection points

TO REMOTE T/H SENSOR A

P67

DO NOT

USE

UNIT DISPLAY (REAR VIEW)

TO OPTIONAL
EXTERNAL
CONNECTIONS

TO LIEBERT XD COOLING
MODULE AND REMOTE
T/H SENSOR B

P64

P67

P66

TO P64 ON ICOM CONTROL BOARD
RED ETHER NET CABLE

TO P66 ON ICOM CONTROL BOARD

TERMINATION PLUG