Troubleshooting – Liebert Little Glass House User Manual

Page 23

Advertising
background image

23

TROUBLESHOOTING

PROBLEM

CAUSE

SOLUTION

No Power

60 HZ: Verify F2 fuse not blown by

checking on/off switch. If not lit, fuse is

blown

50Hz: Verify breaker has not tripped.

Filter Clogged

Clean, or replace filter

Refrigerant loss

Verify leak. If refrigerant system needs

repaired, replace ECM.

Hot Gas Bypass Valve set
incorrectly

Set valve correctly per LGH handbook

Squirrel cage free spinning on
evaporator or condenser blowers

Reattach and tighten squirrel cage to

blower shaft

ECM Not Cooling

Clogged Condenser coil

Clean coil

Compressor trips on thermal
overload.

Open LGH doors and let compressor cool.
Turn ECM on and verify compressor is
energized (humming). Verify cold air is
being discharged from evaporator
discharge (right side of ECM).

Fans blowing warm air

Faulty Compressor

Verify Compressor has failed. Replace
ECM. If electrical component has failed
causing compressor not to run, replace
component.

Excessive opening of doors

Reduce the amount of opening. Suggest
external keyboard tray. Turn ECM off
when opening door.

Enclosure not properly sealed

Verify leak and fix or replace gasket

Condensate draining
continuously

Evaporator drain kinked or
clogged

Remove ECM and verify plastic tubing is
attached to drain and not kinked or
clogged.

Defective motor in blower

Replace motor

Excessive vibration or
noise

Defective squirrel cage in blower

Replace squirrel cage, or reattach and
tighten to blower shaft.

ECM is overloaded

Verify the correct UPS and load on UPS. If
no UPS; verify watt load of equipment
does not exceed ECM rating.

Heat not rejected from room

Verify LGH is located in room with air
circulation and heat rejected from ECM is
sufficiently removed from room.

ECM not cooling

See above

Cabinet is excessively
hot

UAS operation

Verify UAS operation by jumpering
terminals on high temperature stat