Introduction 1, Safety 1.1, Rack system precautions 1.2 – LaCie 12big rack Serial User Manual

Page 2: Lacie 12big rack serial, Quick install guide

Advertising
background image

LaCie 12big rack serial

Introduction

Quick Install Guide

page 2

Introduction

1.

European Regulations

This equipment complies with European Regulations EN
55022 Class A: Limits and Methods of Measurement of Radio
Disturbance Characteristics of Information Technology
Equipments and EN50082-1: Generic Immunity.

USA Federal Communications Commission (FCC)

This equipment has been tested and found to comply with the
limits for a class A digital device, pursuant to part 15 of the
FCC rules.

Safety

1.1.

All plug-in modules and blank plates are part of the fire
enclosure and must only be removed when a replacement
can be immediately added. The system must not be run
without all modules in place.

Permanently unplug the unit if you think that it has become
damaged in any way and before you move it.

• The enclosure can weigh up to 32kg (70.4lb). Do not try to
lift it by yourself.

• Do not lift a populated enclosure by the module handles or
those on the front of the enclosure, they are not designed to
support the weight of the populated enclosure.

• In order to comply with applicable safety, emission and
thermal requirements no covers should be removed and all
bays must be fitted with plug-in modules.

• The enclosure must only be operated from a power supply
input voltage range of 100-120VAC or 200-240VAC.

• The power supply is used as the main disconnect device.
Ensure that the socket outlets are located near the equipment
and are easily accessible.

• The equipment is designed to be operated with two working
power supply modules.

• To prevent overheating do not operate the enclosure with
one power supply removed for more than 30 minutes.

• Disconnect all supply power for complete isolation.

• The power connection should always be disconnected prior
to removal of the Power Supply module from the enclosure.

• A safe electrical earth connection must be provided to the
power cords. Check the grounding of the enclosure before
applying power.

• Provide a suitable power source with electrical overload
protection to meet the requirements laid down in the technical
specification.

Rack System Precautions

1.2.

The following safety requirements must be considered when
the unit is mounted in a rack.

• The rack design must incorporate stabilizing features
suitable to prevent the rack from tipping or being pushed
over during installation or in normal use.

• To avoid the danger of the rack tipping over, do not slide
more than one enclosure out at once.

• When loading a rack with the units, fill the rack from the
bottom up and empty from the top down.

• The rack design should take into consideration the
maximum operating ambient temperature for the unit,
which is 40°C.

• The system must be operated with low pressure rear
exhaust installation (back pressure created by rack doors and
obstacles not to exceed 5 pascals (0.5mm water gauge)).

• The rack must have a safe electrical distribution system.
It must provide over-current protection for the unit and must
not be overloaded by the total number of units installed in
the rack. Consideration of the electrical power consumption
rating shown on the nameplate should be used when
addressing these concerns.

• The electrical distribution system must provide a reliable
earth for each unit in the rack.

• Each power supply in each unit has an earth leakage
current of 1.5mA max at 60Hz, 264VAC per PSU. The
design of the electrical distribution system must take into
consideration the total earth leakage current from all the
power supplies in all the units. The rack may require labelling
with “HIGH LEAKAGE CURRENT. Earth connection essential
before connecting supply”.

• The rack when configured with the units must meet the
safety requirements of UL 60950-1 and IEC 60950-1.

Advertising