Vfs flow sensor – Lochinvar TISUN SPS0500 User Manual

Page 9

Advertising
background image

9

6

VFS flow sensor

Figure 6-1 VFS 1-12 flow ouput signal

VFS 1-12 output signal flow

Assignment of measurement range: 0.26-3.17 gpm is equal to 0.5-3.5V
Flow rate calculation: Q = 0.26gpm +[(U-0.5)V/3V]*2.91gpm

Figure 6-3 VFS 2-40 flow output signal

VFS 2-40 output signal flow

Assignment of measurement range: 0.53-10.6gpm is equal to 0.5-3.5V
Flow rate calculation: Q = 0.53gpm +[(U-0.5)V/3V]*10gpm

Figure 6-2 VFS 1-12 temperature output signal

VFS 1-12 output signal temperature

Assignment of measurement range: 32-212° F is equal to 0.5-3.5V
Temperature rate calculation: T =32° F + [(U-0.5)V/3V]*180°

F

Figure 6-4 VFS 2-40 temperature output signal

VFS 2-40 output signal temperature

Assignment of measurement range: 32-212° F is equal to 0.5-3.5V
Temperature rate calculation: T =32° F + [(U-0.5)V/3 V]*180° F

■ Vortex flow sensor for liquid media.
■ Measures flow rate and temperature for BTU metering
(energy balance, etc.)
■ Zero wear (no moving parts).

Figure 6-5 VFS flow sensor

Item

Pin Configuration

1

Temperature signal (0.5 to 3.5 relative to pin 3)

2

Flow pressure signal (0.5 to 3.5 relative to pin 3)

3

GND (UV)

4

Voltage Supply (+5 VDC) PELV

SL-PS Installation & Operation Manual