Lennox Hearth ELITE SERIES LBC-3824 User Manual

Page 4

Advertising
background image

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

4

Figure 2

Chase Enclosure

A chase is a vertical box-like structure con-

structed to surround the fireplace and chimney.

Refer to

Figure 2 for a typical chase configura-

tion. As with all chimney installations, avoid

overhead obstructions such as trees, power

lines, etc. A chase should be constructed and

insulated just like any outside wall. In a cold

climate, we recommend the base of the chase

should also be insulated between the solid

continuous floor beneath the fireplace and the

chase bottom. Chase insulation in a cold cli-

mate installation is not required for safety.

Chimney Height

The total height of your completed fireplace

system from the surface the fireplace rests on

to the chimney top must not exceed 80 ft

(24.4 m) and must also meet minimum height

requirements. Refer to the minimum system

height chart, below.

Note: Do not insulate the chase cavity with

blown or fill type insulation materials.

LOCATION OF FIREPLACE

Carefully select the proper location for heat

circulation, aesthetics, chimney obstructions

and clearance to side wall(s). With proper pre-

planning, a slight adjustment of a few inches

can save considerable time and expense later

during construction and assembly.

Hearth

Hearth

Optional

Outside Chase

Figure 4

Carefully consider the position of the fireplace

opening with respect to the location of adja-

cent or nearby stairwells, bath or kitchen ex-

haust fans and/or return air registers for forced

air furnaces/air conditioners that could cause

a smoking fireplace condition if the house is

tightly insulated.

When locating the fireplace, consideration must

be given to combustibles and final finishing.

See

Figure 5 and confine the final location of

combustible finish materials to the “Safe Zone.”

Insulate Joists

Same As Ceiling

Draft Stops

Note: Non-

Combustible

Chase

Flashing

must be

Used to

Cover

Chase

Opening

Optional

Insulation

in Outside

Walls of

Chase

Solid

Continuous

Surface

Outside

Base

Insulation

(Thermal Barrier)

8'

(2.4m)

Level

F10FS-2

Firestop

FTF10-CT2

Termination

19"

(483mm)

19"

(483mm)

WARNING: IF INSULATION IS USED, THE

FIREPLACE MUST NOT BE PLACED DI-

RECTLY AGAINST IT. INSULATION OR

VAPOR BARRIERS, IF USED, MUST FIRST

BE COVERED WITH GYPSUM BOARD,

PLYWOOD, PARTICLE BOARD OR OTHER

MATERIAL TO ASSURE INSULATION AND

VAPOR BARRIERS REMAIN IN PLACE.

WARNING: DO NOT PACK OR FILL RE-

QUIRED AIR SPACES WITH INSULATION

OR OTHER MATERIAL. NO MATERIAL IS

ALLOWED IN THESE AREAS.

Note: Local codes may not require firestopping

at the ceiling levels for outside chase installa-

tions. However, it is recommended for safety

and the reduction of heat loss.

MINIMUM SYSTEM HEIGHT

Security FTF10 Pipe

Vertical Installation

14 ft (4.3 m)

One Offset
Two Offsets

16 ft (4.9 m)
24 ft (7.3 m)

Figure 3

ASSEMBLY OUTLINE

Before You Start

Check the inventory list to be sure you have all

necessary parts in good usable condition. Also

check for any concealed damage.
Check the operation of the damper. The dam-

per is controlled through the use of a damper

rod inside the top center of the firebox open-

ing, behind the lintel (Figure 3).
• To CLOSE the damper, PUSH the damper rod

UP and BACK (toward the rear of the fire-

place), until locked in position.

• To OPEN the damper, PULL the damper rod

FORWARD (toward the front of the fireplace)

and DOWN, until locked in position.

To CLOSE damper, PUSH damper rod UP

and BACK (toward rear of fireplace).
To OPEN damper, PULL damper rod DOWN

and FORWARD (toward front of fireplace).

Combustion Air Actuator

Lintel

Damper

CLOSED

Damper

OPEN

~

Damper Rod

Advertising