Specifications, 2 and 3 ton split systems – Liebert Overhead Precision Cooling and Humidity Control Mini-Mate2 User Manual

Page 9

Advertising
background image

60 HZ

50 HZ

CHILLED WATER

3 Tons

3 Tons

Evaporator

MMD40C

MMD39C

Capacity Data BTUH (kW) High Fan Speed

80 F (26.7 C) DB

Total

49,200 (14.4)

49,200 (14.4)

50% RH

Sensible

33,100 (9.7)

33,100 (9.7)

75 F (23.9 C) DB

Total

33,900 (9.9)

33,900 (9.9)

50% RH

Sensible

27,800 (8.1)

27,800 (8.1)

72 F (22.2 C) DB

Total

27,100 (7.9)

27,100 (7.9)

50% RH

Sensible

24,900 (7.3)

24,900 (7.3)

Capacity Data BTUH (kW) Low Fan Speed

80 F (26.7 C) DB

Total

40,700 (11.9)

40,700 (11.9)

50% RH

Sensible

26,900 (7.9)

26,900 (7.9)

75 F (23.9 C) DB

Total

27,700 (8.1)

27,700 (8.1)

50% RH

Sensible

22,300 (6.5)

22,300 (6.5)

72 F (22.2 C) DB

Total

21,700 (6.4)

21,700 (6.4)

50% RH

Sensible

19,800 (5.8)

19,800 (5.8)

60 HZ

50 HZ

AIR COOLED SYSTEM

with Outdoor Condensing Unit

with Centrifugal Condensing Unit

with Outdoor Condensing Unit with Centrifugal Condensing Unit

2 Tons

3 Tons

2 Tons

3 Tons

2 Tons

3 Tons

2 Tons

3 Tons

Evaporator

MMD24E

MMD36E

MMD24E

MMD36E

MMD23E

MMD35E

MMD23E

MMD35E

Condensing Unit

PFH027A

PFH037A

MCD24A

MCD36A

PFH026A

PFH036A

MCD23A

MCD35A

Net Capacity Data*BTUH (kW) High Fan Speed

80 F (26.7 C) DB

Total

25,600 (7.5) 36,900 (10.8)

24,200 (7.1) 34,100 (10.0) 23,800 (7.0)

34,500 (10.1) 22,700 (6.7)

31,800 (9.3)

50% RH

Sensible

20,900 (6.1)

26,600 (7.8)

20,300 (5.9)

28,300 (8.3)

20,200 (5.9)

28,400 (8.3)

19,800 (5.8)

27,400 (8.0)

75 F (23.9 C) DB

Total

23,800 (7.0) 34,200 (10.0)

22,400 (6.6)

31,700 (9.3)

22,100 (6.5)

32,100 (9.4)

21,000 (6.2)

29,600 (8.7)

50% RH

Sensible

20,100 (5.9)

25,700 (7.5)

19,500 (5.7)

27,200 (8.0)

19,400 (5.7)

27,400 (8.0)

19,000 (5.6)

26,400 (7.7)

72 F (22.2 C) DB

Total

22,900 (6.7)

32,900 (9.6)

21,400 (6.3)

30,400 (8.9)

21,200 (6.2)

30,800 (9.0)

20,100 (5.9)

28,300 (8.3)

50% RH

Sensible

19,700 (5.8)

25,200 (7.4)

19,100 (5.6)

26,500 (7.8)

19,000 (5.6)

26,700 (7.8)

18,500 (5.4)

25,700 (7.5)

Net Capacity Data*BTUH (kW) Low Fan Speed

80 F (26.7 C) DB

Total

25,500 (7.5) 36,900 (10.8)

24,000 (7.0)

33,600 (9.8)

23,700 (6.9)

34,000 (10.0) 22,600 (6.6)

31,500 (9.2)

50% RH

Sensible

19,800 (5.8)

26,600 (7.8)

19,300 (5.7)

25,300 (7.4)

19,100 (5.6)

25,400 (7.4)

18,700 (5.5)

24,400 (7.1)

75 F (23.9 C) DB

Total

23,800 (7.0) 34,200 (10.0)

22,300 (6.5)

31,300 (9.2)

22,000 (6.4)

31,700 (9.3)

20,900 (6.1)

29,300 (8.6)

50% RH

Sensible

19,200 (5.6)

25,700 (7.5)

18,500 (5.4)

24,300 (7.1)

18,400 (5.4)

24,600 (7.2)

18,000 (5.3)

23,600 (6.9)

72 F (22.2 C) DB

Total

22,700 (6.7)

32,900 (9.6)

21,300 (6.2)

29,900 (8.8)

21,100 (6.2)

30,400 (8.9)

20,000 (5.9)

28,000 (8.2)

50% RH

Sensible

18,700 (5.5)

25,200 (7.4)

18,100 (5.3)

23,900 (7.0)

18,000 (5.3)

24,100 (7.1)

17,500 (5.1)

23,100 (6.8)

60 HZ

50 HZ

WATER COOLED

GLYCOL COOLED

WATER COOLED

GLYCOL COOLED

2 Tons

3 Tons

2 Tons

3 Tons

2 Tons

3 Tons

2 Tons

3 Tons

Evaporator

MMD24E

MMD36E

MMD24E

MMD36E

MMD23E

MMD35E

MMD23E

MMD35E

Condensing Unit

MCD26W

MCD38W

MCD26W

MCD38W

MCD25W

MCD37W

MCD25W

MCD37W

Net Capacity Data*BTUH (kW) High Fan Speed

80 F (26.7 C) DB

Total

26,600 (7.8) 38,400 (11.3)

23,000 (6.7) 35,200 (10.3) 24,900 (7.3)

35,700 (10.5) 21,300 (6.2)

32,600 (9.6)

50% RH

Sensible

21,300 (6.2)

29,900 (8.8)

19,900 (5.8)

28,700 (8.4)

20,600 (6.0)

28,900 (8.5)

19,300 (5.7)

27,700 (8.1)

75 F (23.9 C) DB

Total

24,600 (7.2) 35,600 (10.4)

21,400 (6.3)

32,700 (9.6)

22,800 (6.7)

33,000 (9.7)

19,800 (5.8)

30,400 (8.9)

50% RH

Sensible

20,400 (6.0)

28,800 (8.4)

19,100 (5.6)

27,600 (8.1)

19,700 (5.8)

27,700 (8.1)

18,500 (5.4)

26,700 (7.8)

72 F (22.2 C) DB

Total

23,400 (6.9)

33,900 (9.9)

20,500 (6.0)

31,300 (9.2)

21,800 (6.4)

31,500 (9.2)

18,700 (5.5)

29,100 (8.5)

50% RH

Sensible

19,900 (5.8)

28,100 (8.2)

18,700 (5.5)

27,000 (7.9)

19,200 (5.6)

27,100 (7.9)

18,700 (5.5)

26,000 (7.6)

Net Capacity Data*BTUH (kW) Low Fan Speed

80 F (26.7 C) DB

Total

26,200 (7.7) 37,400 (11.0)

22,700 (6.7) 34,200 (10.0) 24,500 (7.2)

34,600 (10.1) 21,100 (6.2)

31,800 (9.3)

50% RH

Sensible

20,100 (5.9)

26,700 (7.8)

18,800 (5.5)

25,500 (7.5)

19,500 (5.7)

25,700 (7.5)

18,200 (5.3)

24,600 (7.2)

75 F (23.9 C) DB

Total

24,200 (7.1) 34,400 (10.1)

21,100 (6.2)

31,800 (9.3)

22,600 (6.6)

32,000 (9.4)

19,600 (5.7)

29,600 (8.7)

50% RH

Sensible

19,400 (5.7)

25,800 (7.6)

18,100 (5.3)

24,700 (7.2)

18,700 (5.5)

24,800 (7.3)

17,500 (5.1)

23,700 (6.9)

72 F (22.2 C) DB

Total

23,000 (6.7)

32,900 (9.6)

20,300 (5.9)

30,500 (8.9)

21,500 (6.3)

30,600 (9.0)

18,800 (5.5)

28,300 (8.3)

50% RH

Sensible

18,900 (5.5)

25,200 (7.4)

17,700 (5.2)

24,100 (7.1)

18,200 (5.3)

24,200 (7.1)

17,000 (5.0)

23,200 (6.8)

*The net capacity data has fan motor heat factored in for all ratings and the entering air condition of 72˚F (22.2˚C), 50% RH is the standard rating condition of ASHRAE 127-2001

9

Specifications

2 And 3 Ton Split Systems

Advertising