Warning – LG ELITE ME43BK SP User Manual

Page 7

Advertising
background image

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

7

WARNING

The top of the fireplace is not

zero clearance. Do not place

any insulating material in the

space above the fireplace for a

height of 7 feet from the base of

the fireplace.

WARNING

The header should rest on top

of the metal spacers. Do not

alter the spacers or notch the

header to fit around them. Do

not block the air inlet or outlet

as this will cause the fireplace

to overheat.

3. Do not block the fireplace’s hot air vents or

air inlets as this will cause the fireplace to

overheat.

Figure 5

NOTE: Chase wall and floor must be insulated

in the same manner than the rest of the building

below the attic.

Fireplace Facing

The fireplace should be framed using 2" x 3"

(50mm x 75mm) or heavier lumber.

Figure 10 on Page 10 shows the general

framing layout.

Combustible materials must be installed

flush with the fireplace facing. They may not

project out in front of the fireplace. Non-

combustible materials such as brick, stone or

ceramic tile, may project in front of and/or on

the fireplace facing.

Figure 6

Mantel

A wood mantel, if installed, must be at least

48" (1.2 m) above the base of the fireplace (see

Figure 7). There is no restriction regarding the

length or the width of the mantel.

Figure 7

CEILING/FLOOR

SEPARATION

MUST HAVE THE SAME INSULATION

LOCAL CODE REGULATION FOR CEILING

MUST BE APPLIED TO THE CEILING/FLOOR

SEPARATION, I.E. FIRESTOP, ETC.

MUST HAVE THE SAME FIRE RATING

AS ADJACENT CEILING.

AS ADJACENT CEILING.

ROOF SUPPORT

ATTIC

FIRESTOP

FLASHING

NON COMBUSTIBLE

CHASE TOP

FIREPLACE

2"

7 ft. Min.

FINISHED

WALL

DRYWALL PANEL OR EQUIVALENT

SPACER

2" x 3" MIN.

FIREPLACE

18"

48"

Min.

52"

1"

8"