Lennox International Inc. 2SCU13 User Manual

Page 3

Advertising
background image

# 48283B006

Page 3

Figure 2

Slab Mounting

2° or 2" per 5' slope tolerance away from building
structure.

Discharge Air

Mounting Slab

Ground Level

Building

Structure

Figure 3

Wind Barrier Construction

Prevailing Winter Winds

24"

Wind Barrier

Inlet Air

Inlet Air

Inlet Air

Electrical Wiring

All field wiring must be done in accordance with the
National Electrical Code (NEC) recommendations,
Canadian Electrical Code (CEC) and CSA Standards, or
local codes, where applicable.

Unit must be grounded in accordance with
national and local codes. Failure to ground unit
properly can result in personal injury or death.

WARNING

Refer to the furnace or blower coil Installation Instructions
for additional wiring application diagrams and refer to unit
rating plate for minimum circuit ampacity and maximum
overcurrent protection size.

1. Install line voltage power supply to unit from a properly

sized disconnect switch. Any excess high voltage field
wiring should be trimmed or secured away from the
low voltage field wiring.

2. Ground unit at unit disconnect switch or to an earth

ground. To facilitate conduit, a hole is in the bottom of
the control box. Connect conduit to the control box using
a proper conduit fitting. Units are approved for use only
with copper conductors. 24V Class II circuit connections
are made to the low voltage pigtails. A complete unit
wiring diagram is located inside the unit control box
cover (see also pages 16 and 17 of this instruction).

3. Install room thermostat on an inside wall that is not

subject to drafts, direct sunshine, or other heat sources.

4. Install low voltage wiring from outdoor to indoor unit and

from thermostat to indoor unit (see Figure 4).

5. Do not bundle any excess 24V control wire inside control

box. Run control wire through installed wire tie and tighten
wire tie to provide low voltage strain relief and to maintain
separation of field-installed low and high voltage circuits.

Refrigerant Piping

Field refrigerant piping consists of liquid and suction lines
from the outdoor unit (sweat connections) to the indoor
coil (flare or sweat connections).

Select line set diameters from Table 2 on page 4 to
ensure that oil returns to the compressor. Size vertical

Thermostat Designations

Figure 4

See unit wiring diagram for power supply connections.
If the indoor unit is not equipped with a blower relay,
one must be field supplied and installed.
Do not connect C (common) connection between
indoor unit and thermostat except when required by
the indoor thermostat. Refer to thermostat installation
instructions. C (common) connection between indoor
unit and outdoor unit required for proper operation.

Power

Indoor Unit

Thermostat

Outdoor

Unit

Y1 Outdoor Unit

Heat

Cooling

Indoor Blower

R

W1

Y

G

C

R

W

Y

G

C

C Outdoor Unit

Advertising