Operation

Function of Controls

Operation

• DISPLAY

1) C/O Model

Operation Indicator

• ON while in appliance operation, OFF while in appliance pause.
• Flashing while in disconnection or short in Thermistor. (3 sec off / 0.5 sec on)

Timer Indicator

• ON while in timer mode (on/off), OFF when timer mode is completed or canceled.

Comp. Running Incidator

• While in appliance operation, ON while in outdoor unit compressor running, OFF while in compres-

sor off.

2) H/P Model

Operation Indicator

• ON while in appliance operation, OFF while in appliance pause.
• Flashing while in disconnection or short in Thermistor. (3 sec off / 0.5 sec on)

Timer Indicator

• ON while in timer mode (on/off), OFF when timer mode is completed or canceled.

Defrost Indicator

• OFF except when hot start during heating mode operation or while in defrost control.

■

Cooling Mode Operation

• When the intake air temperature reaches 0.5°C below the setting temp, the compressor and the out-

door fan stop.

• When it reaches 0.5°C above the setting temp, they start to operate again.

Compressor ON Temp

➲

Setting Temp+0.5°C

Compressor OFF Temp

➲

Setting Temp-0.5°C

• While in compressor running, operating with the airflow speed set by the remote control. While in

compressor not running, operating with the low airflow speed regardless of the setting.

■

Healthy Dehumidification Mode

• When the dehumidification operation input by the remote control is received, the intake air tempera-

ture is detected and the setting temp is automatically set according to the intake air temperature.

26°C

≤

Intake Air Temp

➲

25°C

24°C

≤

Intake Air Temp<26°C

➲

Intake Air Temp-1°C

18°C

≤

Intake Air Temp<24°C

➲

Intake Air Temp-0.5°C

Intake Air Temp<18°C

➲

18°C

- 35 -

Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes

LGE Internal Use Only