Stove installation – Lopi Leyden 028-S-75-2 User Manual

Page 17

Advertising
background image

Stove Installation

(for qualified installers only)

17

© Travis Industries

100-01177

4060802

Hearth Stove
Positive
Connection

NOTE:

Most factory-built
chimney manufacturers
make stainless steel
chimney liners, either
flexible or rigid. This
provides a wide variety
of installation options.
Make sure to follow the
manufacturer's
instructions for
installation and support.

Remove damper
or wire it open

Airtight Insulated
Clean-Out

Min. 36"

Combustible
Mantle

NOTE: The entire fireplace and
chimney must be clean, undamaged,
and meet all local building codes
(UBC, etc.). Damage must be
repaired prior to installation. The
chimney must be 15' to 33' tall.

Floor Protection
(See the section
"Floor Protection
Requirements"
for more details)

See the section
"Stove Placement
Requirements" for
minimum clearances
required.

The liner must be
stainless steel connector
or flexible vent. Follow
the liner manufacturer's
instructions for installation
and support.

Cap and flashing
prevents water from
entering

Figure 15

Hearth Stove Direct
Connection

NOTE:
Direct connections require
installation of an airtight,
non-combustible block-off
plate or damper adapter.

Block-off plate or
damper adapter

Remove damper
or wire it open

Airtight
Insulated
Clean-Out

Stainless steel
chimney connector
must Extend 1' past
the block-off plate or
to the flue liner

NOTE: The chimney must have a clay
tile liner. If it does not, the installation
must use a positive connection (full
reline). The entire fireplace and
chimney must be clean, undamaged,
and meet all local building codes (UBC,
etc.). Damage must be repaired prior
to installation. The chimney must be
15' to 33' tall.

Clay
Liner

Floor Protection
(See the section "Floor
Protection Requirements"
for more details)

Combustible Mantle

Min. 36"

See the section
"Stove Placement
Requirements" for
minimum clearances
required.

Figure 16