READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE INSTALLING FIXTURE

This fixture is intended for installation in accordance with the National Electrical Code and local regulations. To

assure full compliance with local codes and regulations, check with your local electrical inspector before

installation. To prevent electric shock, turn off electricity at fuse box before proceeding.

Retain these instructions for maintenance reference.

INSTRUCTION SHEET NO.

IS:4X9EM

A0502

Page 3 of 4

A

COMPANY

631 Airport Road, Fall River, MA 02720

Instructions for replacing EMERGENCY BALLAST:

ALL SERVICING MUST BE PERFORMED BY QUALIFIED PERSONNEL ONLY.

1. This unit has more than one power supply connection point. Make certain that the switch (if the fixture is switched) and

the unswitched lines to the EMERGENCY BALLAST are turned off at the fuse box.

2. To remove SWITCH BOX from ceiling: Disconnect the battery pack inverter connectors (see page 2) located inside the

SWITCH BOX to prevent electrical shock from the battery pack. Disconnect switch and indicator light leads, and
locknut inside SWITCH BOX. Remove SWITCH BOX.

3. Disconnect all EMERGENCY BALLAST connections inside fixture JUNCTION BOX.
4. Disconnect all leads from A/C BALLAST. DO NOT disconnect any wire leads from lamp socket(s). Remove LOCKNUT

from BALLAST PLATE, and remove BALLAST PLATE with A/C BALLAST. See page 2 for detailed instructions on A/C
BALLAST removal and replacement.

5. Loosen RETAINING SCREW on EMERGENCY BALLAST MOUNTING BRACKET, and lift EMERGENCY BALLAST

MOUNTING BRACKET from HOUSING wall.

6. Feed EMERGENCY BALLAST MOUNTING BRACKET and EMERGENCY BALLAST through opening.
7. Remove emergency ballast from MOUNTING BRACKET and replace with new EMERGENCY BALLAST.
8. Re-install all hardware, including fiberglass sleeves over wiring.
9. Re-connect all electrical connections. Follow appropriate wiring diagram on page 4.

SWITCH BOX

JUNCTION BOX

A/C BALLAST

BALLAST PLATE

LOCKNUT

HOUSING

RETAINING SCREW

EMERGENCY BALLAST
MOUNTING BRACKET

VIEW LOOKING INSIDE FIK

SIDE VIEW

INSTALLATION PROCEDURE FOR: 4X9 AND 9X9 MATRIX SERIES RECESSED

COMPACT FLUORESCENT EMERGENCY LIGHTING FRAME-IN KITS