Troubleshooting – Liebert 700-2200 VA User Manual

Page 19

Advertising
background image

19

TROUBLESHOOTING

The information below indicates various symptoms a user may encounter in the
event the PowerSure™ Interactive UPS develops a problem. Use this information
to determine whether external factors cause the problem and how to remedy the
situation.

1. The fault indicator will flash every second to indicate the UPS detected a

problem.

2. An alarm will sound, alerting that the UPS requires attention.
3. One or more additional load/battery level LED segments will be illuminated to

provide a diagnostic aid to the operator, as described below:

A.

UPS fault (fan failure, battery overcharge)
NOTE: The internal fan operates intermittently as needed

B.

UPS failed battery test

D.

UPS shutdown due to output overload time-out

A&B.

UPS shutdown due to main input relay failure/output short circuit

A&D.

UPS shutdown due to over temperature condition

B&D.

UPS shutdown due to command from communication ports

(remote shutdown or SNMP)

The fault indicators will be illuminated indefinitely while battery charger is
operational, or for a maximum of 5 minutes while battery charger is not operational.
If a problem persists consult your dealer, or contact Liebert Technical Support
(LTS). World Wide Technical Support numbers are located at the end of this
section.

Load/ Battery

Level Indicators

Utility High/Low

Utility

Alarm silence/Test

On/Off

“D” indicator

Fault indicator

(flashes every second)

“B” indicator
“A” indicator