AUDIBLE ALARM CONDITIONS

CONDITION

ALARM

Battery mode
(utility failure)

One short beep every ten seconds; more than two
minutes of run time remaining

Low battery

Two short beeps every five seconds; less than two
minutes of run time remaining

Battery replacement

Two second beep every minute

UPS output overload

One short beep every second

UPS fault

Continuous tone

FUSE REPLACEMENT PROCEDURES

FOR 700 VA MODELS

CAUTION: Before changing the supply fuse, turn off the UPS, and unplug the
input cord from the AC input power supply and from the UPS.
1. Remove the fuse holder by inserting a flat blade screwdriver into the slot and

pulling out as indicated in the figure above.

2. Remove the input fuse.
3. Remove the spare fuse from its position by using the screwdriver to push it out.
4. Place spare fuse in the input fuse position, and replace the fuse holder. The

fuse holder will lock into position.

5. Reconnect the input power lead to the UPS, and the input power lead to the

input AC supply.

6. Restart the UPS. The UPS is ready for normal operation.
NOTE: For 1000, 1400, and 2200 VA units press the reset circuit protector button.

Insert flat blade screw

driver into slot and pull
fuse holder out to remove

AC Inlet

Fuse Holder

Input Fuse
Spare Fuse