AC4 Specifications

Ordering Information

Quantity

Part #

Description

AC4

AC4 controller board in enclosure

201258P1

RS232 configuration cable

TM115

Transformer Module 115VAC with two 24VAC outputs (40VA each) and 115VAC receptacle

TM230

Transformer Module 230VAC with two 24VAC outputs (40VA each)

DEVICES CONNECTED

TO INPUTS & OUTPUTS

RS232

Liebert

Challenger

3000

Liebert

Himod

Liebert

Challenger

3000

Liebert

Himod

Zone 1 Devices

Device 1

Device 2

Zone 2 Devices

Device 3

Device 4

Power Requirements

24VAC ±10% of nominal

50/60 Hz, 1.3A, 30VA

Dimensions W x D x H, in. (mm) 14-1/4 x 2-3/4 x 12

(361.95 x 69.85 x 304.8)

Weight (Assembled)

7.68 lbs (3.48 kg)

Enclosure Type

NEMA 1

Liquid Crystal Display (LCD)

Four line, 20 character, backlit

Mounting Surface

Building Wall or Structural Member

Ambient Operating

Environment

32°F to 104°F (0°C to 40°C)

0% RH to 95% RH (non-condensing)

Processor Specifics

Model

Motorola XC68HC812A4

Clock speed

16MHz

Total RAM

32Kb

Total FLASH

4M

Total EEPROM

4K

A/D Resolution (Analog IN)

12 Bit

Clock Type

Real-Time Clock

Clock battery backup type

Lithium Cell (non-replaceable)

Clock battery life

7 years, constant, no power

Communications

Local Communications

RS232

Agency Listings

UL

UL3121

CSA

C22.2 NO. 1010

CE

Yes

FCC Compliance

CFR 47 Part 15

Inputs & Outputs (Quantity)

Digital Inputs (4)

Dry Contact Closure

24VDC, 10 mA

Digital Outputs (4)

24VAC, 3A

Common Alarm Outputs (2)

24VAC, 3A

Typical Configuration