Sidewall direct venting, Vent/air termination – sidewall, Installation & operation manual – Lochinvar Wall Mount Boiler WH 55-399 User Manual

Page 23

Advertising
background image

Vent/air termination – sidewall

23

Installation & Operation Manual

ALTERNATE VENTING ARRANGEMENT

(IF SPACE PERMITS)

BIRD

SCREEN

12”

MIN

12” MIN

15” MAX

COUPLING

TO BOILER

INTAKE AIR

CONNECTION

FROM BOILER

VENT PIPE

CONNECTION

BIRD SCREEN

GRADE OR

SNOW LINE

Figure 4-1C Alternate PVC/CPVC/SS/ Polypropylene Venting
Arrangement (if Space Allows) w/Field Supplied Fittings

VENT / AIR

TERMINATION

12"

MIN.

12"

MIN.

12"

MIN.

Figure 4-2A Clearance to Gravity Air Inlets

BIRD

SCREEN

(TYPICAL)

12”

MIN.

12”

MIN.

12”

MIN.

Figure 4-2B Alternate Clearance to Gravity Air Inlets w/
Field Supplied Fittings

5. Maintain clearances as shown in FIG.’s 4-1A thru 4-3B,

pages 22 - 24. Also maintain the following:
a. Vent must terminate:

• At least 6 feet from adjacent walls.

• No closer than 12 inches below roof overhang.

• At least 7 feet above any public walkway.

• At least 3 feet above any forced air intake within

10 feet.

• No closer than 12 inches below or horizontally

from any door or window or any other gravity air

inlet.

b. Air inlet must terminate at least 12 inches above

grade or snow line; at least 12 inches below the vent

termination; and the vent pipe must not extend

more than 24 inches vertically outside the building

as shown in FIG. 4-1B. Condensate could freeze and

block vent pipe.

c. Do not terminate closer than 4 feet horizontally

from any electric meter, gas meter, regulator, relief

valve, or other equipment. Never terminate above or

below any of these within 4 feet horizontally.

12" (305 MM) MIN

15" (381 MM) MAX

12" (305 MM) MIN

FROM BOILER

VENT PIPE

CONNECTION

TO BOILER

INTAKE AIR

CONNECTION

BIRD SCREEN

GRADE OR
SNOW LINE

Figure 4-1D Alternate SS Venting Arrangement -
Typical Stainless Steel Sidewall Termination of Air and
Vent w/Field Supplied Fittings, Utilizing a Hood Intake

FORCED AIR

INLET

VENT / AIR

TERMINATION

7' MIN. ABOVE ANY

PUBLIC WALKWAY

IF LESS

THAN 10’

36"

MIN.

Figure 4-3A Clearance to Forced Air Inlets

6. Locate terminations so they are not likely to be damaged

by foreign objects, such as stones or balls, or subject to
buildup of leaves or sediment.

4

Sidewall direct venting

(continued)