Troubleshooting, Guide to status indicators, Roubleshooting – Liebert 500-650 VA User Manual
Page 19

15
T
ROUBLESHOOTING
The information below indicates various symptoms a user may
encounter in the event the PowerSure PST experiences a problem. Use
this information to determine whether external factors caused the
problem. See Troubleshooting Chart for suggested remedy.
Guide to Status Indicators
1. The Fault Indicator illuminates, indicating
the UPS detected a problem.
2. An alarm sounds, alerting that the UPS
requires attention. The alarm can be
silenced except for low battery and overload
warning conditions.
3. Mains/Battery Indicator may be illuminated
as a diagnostic aid to the operator, as shown
below:
Fault
(Red)
Mains/Battery
(Green)
Diagnosis/
Audible Alarm
Normal Mode
—
ON
UPS is operating in Normal Mode; no
beep.
—
Flashing
Battery Test has been initiated; no
beep.
Flashing
ON
The unit is overloaded; beep every
half-second
ON
ON
The UPS has failed; continuous beep
Flashing
—
Unit has shutdown due to overload;
continuous beep
ON
—
The UPS shutdown due to failure;
continuous beep
Battery Mode
—
Flashing
The UPS is operating in Battery mode;
beep every 5 seconds.
—
Flashing
UPS battery is low; beep every
half-second
Flashing
Flashing
The unit is overloaded; beep every
half-second
ON
Flashing
The UPS has failed; continuous beep