Troubleshooting, Guide to status indicators, Roubleshooting – Liebert 500-650 VA User Manual

Page 19

Advertising
background image

15

T

ROUBLESHOOTING

The information below indicates various symptoms a user may

encounter in the event the PowerSure PST experiences a problem. Use

this information to determine whether external factors caused the

problem. See Troubleshooting Chart for suggested remedy.

Guide to Status Indicators

1. The Fault Indicator illuminates, indicating

the UPS detected a problem.

2. An alarm sounds, alerting that the UPS

requires attention. The alarm can be

silenced except for low battery and overload

warning conditions.

3. Mains/Battery Indicator may be illuminated

as a diagnostic aid to the operator, as shown

below:

Fault

(Red)

Mains/Battery

(Green)

Diagnosis/

Audible Alarm

Normal Mode

ON

UPS is operating in Normal Mode; no

beep.

Flashing

Battery Test has been initiated; no

beep.

Flashing

ON

The unit is overloaded; beep every

half-second

ON

ON

The UPS has failed; continuous beep

Flashing

Unit has shutdown due to overload;

continuous beep

ON

The UPS shutdown due to failure;

continuous beep

Battery Mode

Flashing

The UPS is operating in Battery mode;

beep every 5 seconds.

Flashing

UPS battery is low; beep every

half-second

Flashing

Flashing

The unit is overloaded; beep every

half-second

ON

Flashing

The UPS has failed; continuous beep

Fault

Indicator

Mains/

Battery

Indicator

!

+

-